D-6
Using RTU Master Mode
Figure D.6 DriveExecutive WIM Linear List Screen
2.
Remove power from the drive to which the wireless connection has
been made. Then electrically connect all drives to create the RTU
Master network. Refer to
System Wiring on page D-6
for network
wiring details.
When wiring an RTU Master network, refer to
Figure D.7
. Connect the
first PowerFlex 4-Class drive (Drive 1) on the network to the WIM using
an AK-U0-RJ45-SC1 splitter cable. Connect its male end into Port 2 on
the bottom of the drive. The WIM must be connected to the Master port
(identified by the letter “M” at the port) of the splitter cable.
Important:
Only one splitter cable can be used on the network, and it
must be used to connect the WIM to the first drive.
Using a 22-RJ45CBL-Cxx Communications Cable, or an appropriate
twisted pair cable and an AK-U0-RJ45-TB2P terminal block connector
(
Figure D.8
), insert the connector into the splitter cable Slave port
(identified by the letter “S” at the port). Then insert the connector on the
cable’s other end into Port 2 on the bottom of the second drive (Drive 2).
For all subsequent PowerFlex 4-Class drives (up to 32 drives total on the
RTU Master network), daisy-chain them together using the same type of
cable and terminal block adapters connected into Port 2 on the bottom of
each respective drive.
System Wiring
Summary of Contents for PowerFlex 22-WIM-N1
Page 1: ...User Manual DSI Wireless Interface Module 22 WIM N1 22 WIM N4S FRN 1 xxx...
Page 4: ...soc ii Summary of Changes...
Page 10: ...P 4 About This Manual Notes...
Page 52: ...4 6 Troubleshooting Notes...
Page 56: ...A 4 Specifications Notes...
Page 96: ...Index 4...
Page 97: ...Index 5...
Page 98: ...Index 6...
Page 99: ......