The RSLinx Classic Lite software must be installed before you can install the
ControlFLASH software. RSLinx software is a communications software package that
you can use with a wide variety of rockwell automation applications and hardware. The
ControlFLASH software uses the RSLinx Classic Lite software to communicate over
Data highway Plus, DFI, DH485, ControlNet, DeviceNet and Ethernet networks.
Before installing the ControlFLASH Firmware Kit, RSLinx must be configured with the
IP address of the controller you wish to upgrade. Ensure that when you run the RSLinx
software from the
"Communications"
menu click
"Configure Drivers"
. Select a
driver of type "
Ethernet Devices
" and add the required IP address to the list.
Stage 1: Installing the ControlFLASH Firmware
Stage 1: Installing the ControlFLASH Firmware
Stage 1: Installing the ControlFLASH Firmware
Stage 1: Installing the ControlFLASH Firmware
This procedure will install Recovery Mode and Secondary Boot firmware.
1)
Run the ‘350720_102_ControlFLASH.msi file.
2)
Click
Next