Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:
1-9
Operating
0 to 2000m (0 to 6,600 ft.)
Storage and Transport
0 to 3000m (0 to 10,000 ft.)
This equipment must not be transported in
unpressurized aircraft flown above 10,000 ft.
Electromagnetic Interference
Tested to the following standards: EN 61326-
1:2006, Class A; EN 61326-3-1:2008, EN 54-4:
1997, A1; EN 61131-2:2007; EN 62061:2005.
Hazardous Location Capability
Suitable for Class I Div 2 Groups A, B, C and
D
Note:
Casing:
Standard AADvance modules also have a plastic casing and are rated IP20:
Protected against solid objects over 12mm (1/2in.) for example "fingers".There is no
specific protection against liquids.
Product Dimensions
Product Dimensions
Product Dimensions
Product Dimensions
Ov
Ov
Ov
Overall Dimensions of Modules with Base Units
erall Dimensions of Modules with Base Units
erall Dimensions of Modules with Base Units
erall Dimensions of Modules with Base Units
Summary of Contents for ics triplex AADvance
Page 7: ......
Page 15: ...Document 553632 ICSTT RM448_EN_P Issue 08 1 5 ...
Page 114: ......
Page 128: ......