Rockwell Automation Publication 20P-TD001K-EN-P - January 2021
43
PowerFlex DC Drive and Field Controller Technical Data
PowerFlex DC Drives and Field Controller I/O Signal and Control Wiring
Eight digital inputs, four digital outputs, three analog inputs, and two analog outputs are available on the standard I/O terminal blocks that
are provided with the drive. One digital input (1…8) must be configured for “Enable”.
More digital and analog I/O is available when using the optional I/O expansion circuit board. See Appendix F - ‘Optional Analog and Digital I/O
Expansion Circuit Board,’ in the PowerFlex Digital DC Drive User Manual, publication
, for more information. You can also use the
optional 115V AC converter circuit board to convert 115V AC to 24V DC digital inputs signals to interface with the digital inputs on the standard
I/O terminal blocks. See Appendix G Optional 115V AC to 24V DC I/O Converter Circuit Board in the PowerFlex Digital DC Drive User Manual,
, for more information. All I/O terminal blocks are on the control board.
I/O Terminal Block Locations
I/O Terminal Block 1 Designations
No.
Signal
Description
Factory Default
Related
Parameter
DC Drive
Field Controller
1
Analog Input 1 (+)
Isolated
(1)
, bipolar, differential,
±10V / 0…20 mA, or 4…20 mA.
Important:
0…20 mA or 4…20 mA operation requires
that switch S9, S10, and S11 on the Control board be in
the “Off” position. Drive damage can occur if the
switch is not in the correct position that is based on
the type of input signal. See “DIP switch and Jumper
Settings” in the PowerFlex Digital DC Drive User
.
Max ±10V, Max 0.25 mA.
(1) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
1 “Speed Ref A”
5 “Current Ref A”
70 [Anlg In1 Sel]
2 Analog Input 1 (–)
3 Analog Input 2 (+)
0 “Off”
75 [Anlg In2 Sel]
4 Analog Input 2 (–)
5 Analog Input 3 (+)
0 “Off”
80 [Anlg In3 Sel]
6 Analog Input 3 (–)
7 +10V Pot Reference
2…5k
Ω
load. Max ±10V, Max 10 mA.
—
—
8 –10V Pot Reference
9 Pot Common
For (+) and (–) 10V pot references.
10 PE ground
PE ground to drive chassis.
Terminal Block 1
Terminal Block 3
Terminal Block 4
Terminal Block 2