Rockwell Automation Publication 20P-TD001K-EN-P - January 2021
23
PowerFlex DC Drive and Field Controller Technical Data
Field Circuit (Terminals U1, V1)
• 230V ±10%, 1Ph
• 400V ±10%, 1Ph
• 460V ±10%, 1Ph
Control Circuit (Terminals U2, V2)
• 115V ±15% or 230V ±15%, 1Ph
DC Output Voltages
The output voltages that are listed in these two tables take into account an AC input undervoltage within the stated tolerance limits and a
voltage drop of 4% due to an AC input line reactor. It is the same as the rated armature voltage suggested for the connected motor.
IMPORTANT
For only frame B and C drives, a jumper must be placed between terminals SA-SB when 115V AC input power is used
for the control circuit. See Frame B Drives SA-SB Terminal Block Location on page
and Frame C Drives SA-SB
Terminal Block Location on page
for terminal block locations.
Armature Circuit
AC Input Voltage
DC Output Armature Voltage (Terminals C & D)
(Terminals U, V, W)
Two Quadrant Drive
Four Quadrant Drive
230V ±10%, 3Ph
260V
240V
400V ±10%, 3Ph
470V
420V
440V ±10%, 3Ph
530V
460V
460V ±10%, 3Ph
560V
480V
480V ±10%, 3Ph
580V
500V
575V ±10%, 3Ph
680V
600V
690V ±10%, 3Ph
810V
720V
Field Circuit
AC Input Voltage
DC Output Field Voltage
(1)
(Terminals C1 & D1)
(1) The maximum field voltage is equal to 0.85 x AC input line voltage
(Terminals U1 & V1)
Fixed Field
Adjustable Field
230V ±10%, 1Ph
200V
200V
400V ±10%, 1Ph
310V
310V
460V ±10%, 1Ph
360V
360V