PowerFlex DC Drive and Field Controller Technical Data
Fiber-optic Kits
Fiber-optic card is not required. It can be used for
communication between a PowerFlex DC drive and field
controller. For more information on fiber-optic cards, see
, PowerFlex DC Fiber-optic Interface
Option Module Installation Instructions.
Overvoltage Protection Devices
When the PowerFlex DC Field Controller is used to supply a very
inductive load like a motor/generator field or an electromagnet,
an overvoltage protection device (voltage clamp) and
dampening resistor must be installed on the field controller
load. See the PowerFlex DC Field Controller Voltage Clamp
Installation Instructions, publication
, for details.
These tables identify the voltage clamp and dampening resistor
kits.
Communication Option Kits
Description
Cat. No.
BACnet MS/TP RS-485 communication adapter
20-COMM-B
ControlNet communication adapter (coaxial)
20-COMM-C
DeviceNet communication adapter
20-COMM-D
EtherNet/IP™ communication adapter
20-COMM-E
Dual-port EtherNet/IP™ communication adapter
20-COMM-ER
HVAC communication adapter
20-COMM-H
Modbus/TCP communication adapter
20-COMM-M
PROFIBUS DP communication adapter
20-COMM-P
ControlNet communication adapter (fiber)
20-COMM-Q
RS-485 DF1 communication adapter
20-COMM-S
External communications kit power supply
20-XCOMM-AC-PS1
External DPI communications kit
20-XCOMM-DC-BASE
External DPI I/O option board
(1)
(1) For use only with external DPI communications kits 20-XCOMM-DC-BASE.
20-XCOMM-IO-OPT1
USB converter
(2)
(2) Includes 2 m USB, 20-HIM-H10, and 22-HIM-H10 cables.
1203-USB
Personal Computer Programming Software
Description
Cat. No.
Connected Components Workbench™ (CCW) software
(1)
(1) Download available for free at
DriveTools™ SP software
(2)
(2) Available to order through the ‘How to Buy’ link at
http://
ab.rockwellautomation.com/Drives/Software/9303-DriveTools-SP#overview
.
Studio 5000® environment
(3)
(3) For more information on the Studio 5000 environment, see
www.rockwellautomation.com/en-us/products/software/factorytalk/designsuite/
studio-5000/studio-5000-logix-designer.html
Description
Cat. No.
Fiber-optic card
20P-S5H781
Fiber-optic cable kit
• 3 m (9.8 ft)
• 5 m (16.4 ft)
SK-20P-2950
SK-20P-29501
Voltage Clamp Kits
Field Controller Specifications
AC Input Voltage
Output Amp
Rating
Frame Size
Voltage Clamp
Cat. No.
200
17…120
A
23P-FCOVPD-B-FA
200
245…570
B
23P-FCOVPD-B-FB
500
17…120
A
23P-FCOVPD-D-FA
500
245…570
B
23P-FCOVPD-D-FB
Dampening Resistor (RB) Kit Selection
Field Controller
AC Input Voltage
Range (Vrms)
RB Resistor
Value Ohms
RB Resistor Size
Watts
RB Resistor Kit
Cat. No.
(1)
(1) Resistor kits are IP00 / Open Type and must be installed in an enclosure.
60…100V
220
930
23P-FC-RB100
101…200V
390
930
23P-FC-RB200
201…300V
680
930
23P-FC-RB300
301…400V
1000
930
23P-FC-RB400
401…500V
1200
930
23P-FC-RB500