Rockwell Automation Publication 442G-UM002A-EN-P - December 2016
35
Use the Multifunctional Access Box in an Integrated Safety Controller-based System
Chapter 3
Configuration Ownership –
Reset Ownership
Configuration ownership must be established when a new safety I/O module
is added to a project and any time there is a change in one of the following
items.
• EtherNet/IP address
• Safety Network Number
• GuardLogix slot number
• GuardLogix Safety Network Number
• Communication path from GuardLogix controller to module
If any of these items change, the connection between the GuardLogix
controller and the module is lost, and the yellow yield in the project tree
appears. Reset ownership to re-establish the connection by using this
procedure.
1. From the Module Properties dialog box, choose the Safety tab. You see
the Safety dialog box.
2. Click Reset Ownership to re-establish the connection.
3. Click yes to continue with ownership reset.
IMPORTANT
When replacing an access box, if the controller does not automatically re-
establish the safety connection, it may be necessary to reset the ownership
and the SNN.
IMPORTANT
When replacing a device, if the replacement device was used previously and
if the connection is local (as shown on the safety tab in RSLogix 5000), the
device must first be reset to out-of-box condition. Refer to “Resetting a
Module to Out-of-box Condition” in publication