The Adapter module contains two sets of firmware. The normal firmware is
the operational firmware and allows connections from a Logix Controller. The
Recovery firmware is used to update the firmware in the I/O modules and help
diagnose problems. The normal and Recovery firmware are updated with
separate ControlFLASH files.
Before starting check that:
•
RSLinx® Gateway has been installed and configured
•
The BOOTP server has been configured with the MAC address and
suitable IP address for the 1715-AENTR
•
The correct ControlFLASH file for the 1715-AENTR module or I/O module
has been installed
•
If updating 1715 I/O module firmware, ensure that the 1715-AENTR
Recovery mode firmware from 1715 revision 3.001 or later is installed and
running (Recovery mode firmware revision 1.011 or later)
Dual 1715-AENTR modules are updated at the same time.
Each I/O module is updated separately, even if it is fitted to a dual termination
assembly.
Update procedure:
•
Run the ControlFLASH program
•
Select the type of module from the list
•
Browse to the 1715-AENTR and open it, open the Backplane, then select
the module to be updated.
•
Select the version of firmware to be sent to the module
•
Update the module
•
The firmware will be downloaded and stored on the module - this will
take between 2 minutes and 25 minutes
•
Control FLASH will report the success or failure of the update
•
Repeat for other modules that need to be updated
See document
ControlFLASH firmware Upgrade Kit User Manual
in the Literature Library for detailed instructions for using ControlFLASH
When updating the firmware, it is recommended that RSWho is not actively browsing the 1715-AENTR or the associated I/O modules.
When updating the firmware, it is recommended that RSWho is not actively
browsing the 1715-AENTR or the associated I/O modules.