Chapter 2 Installation Instructions
The module also monitors the input data paths and can detect faults within
each input channel. A visual indication of the module status and individual
channel status is provided by an array of front panel indicators and can be
connected to tags within the Studio 5000 Logix Designer® application.
The termination assemblies can accept one or two input modules. Each
termination assembly provides passive signal load termination and over-
voltage protection for each input channel. The system provides flexible input
connectivity by mating specific termination assemblies with the relevant
number of input modules.
Field Loop Circuits for Analog Inputs
These circuits can be used for simplex and duplex configurations of analog
input modules. Fit a suitably rated fuse,“F1” in each circuit to help protect the
field wiring, terminal block and 4mA -20mA current generator.
This field loop connection method is used for two-wire field devices.
Figure 46 - Two-wire Analog Input Field Loop Circuit
This field loop connection is used for three-wire analog field devices. Fit a
suitably rated fuse, “F2” in each circuit to help protect the field wiring, terminal
block and 4mA -20mA current generator.
Shield
Required
Terminal
Blocks
OV
Termination
Assembly
+24V DC
4…20 mA
2-Wire Analog Input
50 mA
120Ω
32116 M
F1