Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
111
Chapter 2 Installation Instructions
5. Place the new module on to the dowel pin on the I/O base unit, see
page
.
6. Push the module in until the connectors are fully mated.
The status indicators listed in
illuminate depending on which module
you are installing. The table is a quick installation reference. For more detailed
status indicator information, see
7. Turn the locking screw on the front of the module a 1/4 turn clockwise to
lock
,
see
page 104
.
• The Redundancy Status indicator of the 1715-IB16D digital input
module shows RED when the screw is locked.
• The Redundancy Status indicator of the 1715-IF16 analog input module
shows RED when the screw is locked.
The module enters its start-up sequence. This takes approximately
3 seconds.
If the module is the first module in a TA group with a running adapter, it
displays the following status indicators. See
.
32069 M
Table 14 - Start-up Sequence
1715-IB16D, 1715-OB8DE, 1715-IF16, and 1715-OF8I Modules
Indicator
Status
Module Status
Green
Redundancy Status
Off
Network Status
Red
Channel 0…7, 8…15
Off