112
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Chapter 2 Installation Instructions
8. If the module is installed next to other modules that are already online,
the start-up sequence completes.
When startup is complete, the status indicators light as follows.
If the module fails to go online, see the troubleshooting guide in
Install Slot Filler Covers
To install the slot filler covers, follow these steps.
1. Place a slot filler cover on the empty slot.
2. Screw the clamp screw 90° to the lock position by using a 9 mm
screwdriver.
Remove Modules
Modules can be removed online without shutting down the system or
upsetting the process in redundant configurations only. However, pulling out
simplex module impacts the process.
Table 15 - First Module in TA Group
1715-IB16D, 1715-OB8DE, and 1715-IF16 Modules
1715-OF8I Module
Indicator
Status
Indicator
Status
Module Status
Green
Module Status
Green
Redundancy Status
Green
Redundancy Status
Red to steady green
Network Status
Amber
Network Status
Amber
Channel 0…7, 8…15
Off
Channel 0…7
Off
1715-IB16D, 1715-OB8DE, 1715-IF16 Modules
1715-OF8I Module
Indicator
Status
Indicator
Status
Module Status
Green
Module Status
Green
Redundancy Status
Green
Redundancy Status
Red to steady green
Network Status
Green
Network Status
Amber
Channel 0…7, 8…15
Inputs show Green;
Outputs show Amber
Channel 0…7
Inputs show Green;
Outputs show Amber
CH1
CH1
CH1
CH1
CH1
CH1
CH1
CH1
TERMINAL IDENTITY
AOTA
Dual.
Ethernet 1
Ethernet 2
Reset
Ethernet 1
Ethernet 2
Reset
Rack Status
Module Status
Redundancy Status
Network Status
Rack Status
Module Status
Redundancy Status
Network Status
Slot Filler Covers
32078 M