84
Rockwell Automation Publication 1715-UM001J-EN-P - December 2020
Chapter 2 Installation Instructions
Figure 40 - Connections to 1715-TASOB8DE and 1715-TADOB8DE Digital Output Termination Assembly
8-channel Simplex/Duplex
Apply a minimum tightening torque of 0.5 N•m (0.37 lb•ft) to the terminal
screws.
The 24V DC field voltages VFIELD 1 and VFIELD 2, used by the output module
for the output field voltages, are connected at the terminal blocks and fed via
two replaceable 10 A fuses, F1 and F2. These fuses give protection for the output
module against field faults. Field OV
(
VFIELD RTN) is also routed from the
output module connectors to the terminal block.
Figure 41 - 1715-TASOB8DE Digital Output Simplex Termination Assembly Connections
OV
OV
OV
V1 +
+
V2
V1 +
V2 +
OV
To
Next
TA
(if fitted)
TB1
TB2
TB3
TB4
CH0
CH2
CH4
CH6
CH1
CH3
CH5
CH7
32105 M DO TA Field
24V DC
24V DC
VFIELD RTN OV
DO CH0
DO CH1
DO CH2
DO CH3
DO CH4
DO CH5
DO CH6
DO CH7
F2
F1
Digital Output Module
Fail Safe Channel
Array
32103 M DO Simplex
Output Connections