20
Rockwell Automation Publication 1609-UM009D-EN-P - February 2021
General Information 1609-D and 1609-B UPS
USB Communication Port
The UPS supports a USB communication port for the end user
to connect with a computer. The user can monitor all the UPS
status through the USB port if the 1609 UPS Management
Software is installed in the computer. The software is stored
in the CD and can be found in the accessory bag.
Manual or Remote Enable/
Disable of UPS Output
Selection
The 1609 UPS output is designed to be manually or remotely enabled or
disabled. User is required to enable or disable the remote function switch
on the front panel.
•
Selected 'DISABLE' for Manual Enable/Disable the UPS Output.
•
Selected 'ENABLE' for Remote Enable/Disable the UPS Output.
Manual Enable/Disable/Self-
test
The Power Button on the front of the UPS is used to
manually enable or disable the output of the 1609-D UPS.
To enable the 1609-D UPS, press and hold the power
button until one beep is heard.
To disable the 1609-D UPS, press and hold the power button until three beeps
are heard, then release immediately (takes approximately three seconds).
To perform a self-test, press and hold the power button until two beeps are heard,
then release immediately. (The UPS must operate for at least four hours before
executing this function)
Remote Enable/Disable
An external switch that is connected to the Dry I/O terminals 7 and 8 is required
to remotely Enable or Disable the UPS output.
To enable the UPS, close the switch
that is connected to the Dry I/O
terminals 7 and 8.
To Disable the UPS, open the
switch that is connected to the
Dry I/O terminals 7 and 8.
REMOTE FUNCTION
ENABLE
DISABLE
8 7 6 5 4 3 2 1
R
R
R
SW
24 Vdc