1609-EXBAT Installation Instructions
1609-EXBAT Installation Instructions
Battery Wiring and
Installation
Only use the battery wires provided with catalog number 1609-EXBAT.
1.
To access the battery compartment, remove the six screws and the battery
door.
2.
Remove the battery container, jumpers, and wire harness from the battery
compartment.
3.
Place the battery container and batteries onto a flat surface.
4.
Use the provided jumper wires to connect the batteries in series.
5.
Connect the positive terminal (red) of the battery to the negative terminal
(black) of another battery.
IMPORTANT
The 1609-EXBAT requires (6) 12V batteries, which are not included. See
for more information.
WARNING:
A disconnect switch must be provided by others for DC output
circuit. To reduce the risk of fire, connect only to a circuit with branch circuit
overcurrent protection for 35 amperes rating in accordance with the National
Electric Code, ANSI/NFPA 70.
Before connecting a battery pack to UPS, the emergent disconnecting device
must be provided between the UPS and battery pack.