24
Rockwell Automation Publication 1609-UM009D-EN-P - February 2021
Troubleshooting
8
Over Voltage from The Output
of AVR
The UPS has detected an
over voltage on the output
of AVR and disabled its
output.
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are
within its specification.
To clear fault, follow the
and if the problem persists, contact Technical
Support.
9
Under Voltage from The Output
of AVR
The UPS has detected low
voltage on the output of
AVR and disabled its
output.
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are
within its specification.
To clear fault, follow the
and if the problem persists, contact Technical
Support.
10
Fan Failure
The UPS has detected that
the fan of the UPS has
failed and disabled its
output.
To clear fault, follow the General Clear Fault Procedure described above and if the Fan Failure persists,
contact Technical Support.
11
Charger Failure
The UPS has detected that
the battery charger circuit
has failed; however, the
UPS continues running.
Clear this fault by removing the input utility voltage and batteries then plug the batteries back in place
and turn the input utility voltage back on. Enable the UPS output to verify the fault.
If the Charger Failure persists, contact Technical Support.
12
TMOV Failure
The UPS has detected that
the MOV circuit has failed;
however, the UPS
continues enabling the
output.
Schedule to have a qualified electrician replace the MOV board (1609-SPD).
Remove the input utility power before service on this 1609-SPD due to risk of electrical shock.
13
Missing Battery
The UPS has detected that
the batteries are missing;
however, the UPS
continues enabling the
output.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for
24 hours.
To clear fault, follow the
. If the battery status still indicates Missing
Battery, new batteries are required.
14
Replace Batteries
The UPS has detected that
the batteries are bad;
however, the UPS
continues running.
Have a qualified electrician verify the battery connection for good contact and charge the batteries for
24 hours.
To clear fault, follow the
. If the battery status still indicates Replace
Battery, new batteries are required.