A-2
LiquiFlo AC Power Modules, Hardware Reference Version 6.4
Table A.2 – Environmental Conditions
Condition
Specification
Operating Temperature (inside an enclosure)
0
°
C
to 55
°
C
*
(
32
°
F
to
131
°
F
)
*
User-supplied cabinet air cooling system must provide adequate heat dissipation to maintain an internal
temperature not to exceed 55
°
C. Refer to table 2.1 for drive air watts loss.
Storage Temperature (Ambient)
-40
°
C
to
65
°
C
(−
40
°
F
to
149
°
F
)
Humidity
5% to 95% (non-condensing)
Table A.3 – Terminal Strip Input Specifications
Signal Type
Terminal(s)
Specification
Speed Reference Input
12-15
10 V (@ 50 K ohm input
impedance or 20 mA)
Digital Inputs (1 - 8)
16
+24 VDC Isolated Supply
17
Remote/Local (Default)
18
Ramp1/Ramp2 (Default)
19
Forward/Reverse
(Default)
20
Function Loss
21
Run/Jog
22
Reset
23
Stop
24
Start
Table A.4 – Terminal Strip Output Specifications
Signal Type
Terminal(s)
Specification
Analog Output
10 -11
scaled signal
0-10 VDC or 4-20 mA
No Connection
26
There is no connection to
terminal 26.
Common
27
+24 VDC common
Summary of Contents for 41LR4060
Page 6: ...IV LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 8: ...VI LiquiFlo 2 0 AC Drive User Manual ...
Page 10: ...VIII LiquiFlo 2 0 AC Drive User Manual ...
Page 12: ...1 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 30: ...2 18 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 40: ...3 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 50: ...4 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 78: ...7 22 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 90: ...9 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 96: ...B 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 98: ...C 2 LiquiFlo 2 0 AC Drive User Manual ...
Page 100: ...D 2 LiquiFlo 2 0 AC Drive User Manual ...
Page 102: ...E 2 LiquiFlo 1 5 AC Power Modules Hardware Reference Version 1 2 ...
Page 107: ......