Wiring the Regulator Board and RMI Board Terminal Strips
7-13
Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring a Remote/Local Input
16
+24 VDC Power Supply
Current limited for remote input logic use only.
17
Digital Input 8
(Default - Remote/Local)
Digital input 8 is control function programmable through
parameter P.007.
!
ATTENTION:
If a maintained start contact is used when the control source = rE, switching
from local to remote from the terminal strip will cause power to be applied to the motor if
the remote start contact is closed. Stay clear of rotating machinery in this case. Failure to
observe this precaution could result in bodily injury.
The following parameters must be set:
•
P.000:Control Source (Only active when P.000 = rE)
•
P.006:Second Menu Password
•
P.007:Terminal Strip Digital Inputs Configure (Selects and
assigns a control function to digital inputs 6 to 8)
•
P.008:Terminal Strip Speed Reference Source
(Analog, Motor Operated Potentiometer (MOP), or Preset
Speeds)
Note that based on the settings of parameters P.000, P.007,
P.008, and r.030 if an RMI board is used, the following
parameters can affect digital input 8:
•
P.023:MOP Accel/Decel Time
•
P.024:MOP Reset Configuration
•
P.031 to P.038: Preset Speeds 1-8
Refer to the LiquiFlo Software Start-Up and Reference
manual for additional information.
Terminal 17 On = Local Control
Diagram shows factory setting.
Summary of Contents for 41LR4060
Page 6: ...IV LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 8: ...VI LiquiFlo 2 0 AC Drive User Manual ...
Page 10: ...VIII LiquiFlo 2 0 AC Drive User Manual ...
Page 12: ...1 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 30: ...2 18 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 40: ...3 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 50: ...4 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 78: ...7 22 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 90: ...9 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 96: ...B 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 98: ...C 2 LiquiFlo 2 0 AC Drive User Manual ...
Page 100: ...D 2 LiquiFlo 2 0 AC Drive User Manual ...
Page 102: ...E 2 LiquiFlo 1 5 AC Power Modules Hardware Reference Version 1 2 ...
Page 107: ......