Rockwell Automation Publication 1766-UM001O-EN-P - September 2021
245
Appendix F MicroLogix 1400 Distributed Network Protocol
DNP3 Device Attribute
Object
The Device Attribute object can be used to identify DNP3 Slave devices.
With the controller, some of the variations are written so that you can read or
write your own strings in your application.
The object group of the Device Attribute object is 0. The supported range of the
variation is 211…255.
The R/W property shows if the object is Read Only, Read, or Write. If the R/W
property is writable, the value which was written by DNP3 master device is
stored to non-volatile memory.
The object group of the Device Attribute is 0. The supported range of the
variation is 211…255.
Object Flags for Analog Output for Series B and Series C controllers
Bit Offset
Name
Description
0
ONLINE
0 when the controller is or was in Non-executing mode.
1 when the controller is or was in Executing mode and the configuration file does not exist.
May be 1 when the controller is in Executing mode and the configuration file exists.
1
RESTART
0 when the controller is or was in Non-executing mode.
0 when the controller is or was in Executing mode and the configuration file does not exist.
May be 1 when the controller is in Executing mode and the configuration file exists.
2
COMM_LOST
3
REMOTE_FORCED
4
LOCAL_FORCED
5
reserved
6
reserved
7
reserved
Object Group 0, Variations for Attribute Set 0
Variation
Read /Write Attribute
Data Type
Length in Bytes
(Series A)
Max Length in
Bytes (Series B
and Series C)
Description
Value (Series A)
Value (Series B)
211
Read Only
VSTR
27
0 for DNP3
Identifier of support for user-
specific attributes
Returns the identifier for
user-specific attributes.
Rockwell Automation, Inc.,
1
Returns the identifier for
user-specific attributes.
"", NULL for DNP3.
212
Read Only
UINT
4
2
Number of master-defined Data-
Set prototypes
0
0
213
Read Only
UINT
4
2
Number of outstation-defined
Data-Set prototypes
0
The configured number in
the DNP3 Slave
Application Layer
Configuration file.
10, max
214
Read Only
UINT
4
2
Number of master-defined Data-
Sets
0
0
215
Read Only
UINT
4
2
Number of outstation-defined
Data-Sets
0
The configured number in
the DNP3 Slave
Application Layer
Configuration file.
10, max
216
Read Only
UINT
4
2
Max number of binary outputs per
request
10
10
217
Read Only
UINT
4
2
Local timing accuracy
10,000 in microseconds
218
Read Only
UINT
4
2
Duration of timing accuracy
0 in seconds
219
Read Only
INT
1
1
Support for analog output events 0
0
220
Read Only
UINT
4
2
Max analog output index
256*3
221
Read Only
UINT
4
2
Number of analog outputs
0…256*3