![Rockwell Automation 1766-L32AWA User Manual Download Page 158](http://html.mh-extra.com/html/rockwell-automation/1766-l32awa/1766-l32awa_user-manual_1475374158.webp)
158
Rockwell Automation Publication 1766-UM001O-EN-P - September 2021
Appendix C Troubleshoot Your System
Extended Error Information Field
Check the extended error information field when a non-zero value is present
in the module error field. See
.
Hardware Errors
General or module-specific hardware errors are indicated by module error
code 2.
Configuration Errors
If you set the fields in the configuration file to invalid or unsupported values,
the module ignores the invalid configuration, generates a non-critical error,
and keeps operating with the previous configuration.
lists the configuration error codes defined for the module.
Error Codes
If no errors are present in the module error field, the extended error information field
is set to zero.
Table 19 - Extended Error Codes for 1762-IF2OF2
Error Type
Hex Equivalent
(1)
Module Error
Code
Extended Error
Information Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no additional information
X201
001
0 0000 0001
Power-up reset state
Hardware-Specific Error X210
001
0 0001 0000
Reserved
Configuration Error
X400
010
0 0000 0000
General configuration error; no additional information
X401
010
0 0000 0001
Invalid input data format selected (channel 0)
X402
010
0 0000 0010
Invalid input data format selected (channel 1)
X403
010
0 0000 0011
Invalid output data format selected (channel 0)
X404
010
0 0000 0100
Invalid output data format selected (channel 1)
(1) X represents “Don’t Care”.
Table 20 - Extended Error Codes for 1762-IF4 and 1762-OF4
Error Type
Hex Equivalent
(1)
Module Error
Code
Extended Error
Information Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no additional information
X201
001
0 0000 0001
Power-up reset state
Hardware-
Specific Error
X300
001
1 0000 0000
Reserved
Summary of Contents for 1766-L32AWA
Page 10: ...10 Rockwell Automation Publication 1766 UM001O EN P September 2021 Table of Contents Notes ...
Page 302: ...302 Rockwell Automation Publication 1766 UM001O EN P September 2021 Glossary Notes ...
Page 308: ...308 Rockwell Automation Publication 1766 UM001O EN P September 2021 Index Notes ...