Rockwell Automation Publication 1766-UM001O-EN-P - September 2021
Appendix F MicroLogix 1400 Distributed Network Protocol
For example, if you want to trigger an event for an analog point every 15
minutes, you should set the TE bit every 15 minutes by the ladder logic. But, in
this case, you may not want the state change events to be generated. Then, set
the bit DCE. You can get the timed events every 15 minutes.
Related Configuration File Number:
•
16-bit Counter Config File Number
•
32-bit Counter Config File Number
•
16-bit Frozen Counter Config File Number
•
32-bit Frozen Counter Config File Number
•
16-bit Analog Input Config File Number
•
32-bit Analog Input Config File Number
•
Short Floating Point Analog Input Config File Number
For Counter type data, you can configure Threshold information in the
Configuration file. Each element can be configured to the threshold value for
each point. A counter event is generated if the absolute value of the difference
between the present value of a counter point and the value that was most
recently queued as an event for that point exceeds the threshold value that was
configured in this file.
Related Configuration File Numbers:
•
16-bit Counter Threshold Config File Number (In Series B and Series C)
•
32-bit Counter Threshold Config File Number (In Series B and Series C)
For Analog Input type data, you can configure deadband information in the
Configuration file. Each element can be configured to the deadband value for
each point. An analog input event is generated if the absolute value of the
difference between the present value of an analog input point and the value
that was most recently queued as an event for that point exceeds the deadband
value that was configured in this file.
Class and Object Configuration for Other Input Data Type
Bit Offset
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Element 0
F7
F6
F5
F4
F3
F2
F1
F0
r
r
DCE
TE
r
r
C1
C0
Element 1
F7
F6
F5
F4
F3
F2
F1
F0
r
r
DCE
TE
r
r
C1
C0
Element 2
F7
F6
F5
F4
F3
F2
F1
F0
r
r
DCE
TE
r
r
C1
C0
Element 3
F7
F6
F5
F4
F3
F2
F1
F0
r
r
DCE
TE
r
r
C1
C0
Element 4
F7
F6
F5
F4
F3
F2
F1
F0
r
r
DCE
TE
r
r
C1
C0
Element 5
F7
F6
F5
F4
F3
F2
F1
F0
r
r
DCE
TE
r
r
C1
C0
…
r: reserved
C1/C0: Class level, 0…3
TE: Trigger Event for the point (In Series B and Series C)
DCE: Disable Change of state Event for the point (In Series B and Series C)
For other Inputs, Element _0 for data index 0
F7…F0: Object Flags, FLAG7/FLAG6/FLAG5/LOCAL_FORCED/REMOTE_FORCED/COMM_LOST/RESTART/ONLINE
Word Offset
Description
Element 0
Threshold for point 0
Element 1
Threshold for point 1
Element 2
Threshold for point 2
Element 3
Threshold for point 3
Element 4
Threshold for point 4
Element 5
Threshold for point 5
…