1606-XLE80E-2 24V, 3.3A; Single Phase Input
10000108328
(Version 00)
www.ra.rockwell.com
Page 13
18.
S
AFETY
Input / output separation
SELV
IEC/EN 60950-1
PELV
EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 5MOhm
input to output, 500Vdc
PE resistance
< 0.1Ohm
between housing and PE terminal
Touch current (leakage current)
typ. 0.16mA
100Vac, 50Hz
typ. 0.24mA
120Vac, 60Hz
typ. 0.41mA
230Vac, 50Hz
< 0.22mA
110Vac, 50Hz
< 0.32mA
132Vac, 60Hz
< 0.57mA
264Vac, 50Hz
19.
D
IELECTRIC
S
TRENGTH
To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit
shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off when
unnoticed earth faults occur.
Fig.
19-1 Dielectric strength
A B C
Type test
60s
2500Vac
3000Vac
500Vac
Factory test
5s
2500Vac
2500Vac
500Vac
Field test
5s
2000Vac
2000Vac
500Vac
A
C
N
L
Input
Earth, PE
Output
-
+
B
Type tests and factory tests:
Conducted by the manufacturer. Do not repeat test in field!
Rules for field test:
Use appropriate test equipment which applies the voltage with a slow ramp!
Connect L and N together as well as all output poles.
The output voltage is floating and has no ohmic connection to ground.