1606-XLE80E-2 24V, 3.3A; Single Phase Input
10000108328
(Version 00)
www.ra.rockwell.com
Page 10
14.
T
ERMINALS AND
W
IRING
All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each other (input below, output above) to
help in error-free wiring.
Type
Screw
terminals
Solid
wire
0.5-6mm
2
Stranded
wire
0.5-4mm
2
American wire gauge
20-10 AWG
Ferrules
Allowed, but not required
Wire stripping length
7mm / 0.275inch
Screwdriver
3.5mm slotted or Pozidrive No 2
Recommended tightening torque
0.8Nm, 7lb.in
Instructions:
a)
Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.
b)
Follow national installation codes and installation regulations!
c)
Ensure that all strands of a stranded wire enter the terminal connection!
d)
Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e)
Do not use the unit without PE connection.
f)
In order to fulfill GL requirements, unused terminal spaces must be closed.