Rockwell
Automation
1606-XLE80E-2 24V, 3.3A; Single Phase Input
10000108328
(Version 00)
www.ra.rockwell.com
Page 3
5.
AC-I
NPUT
AC
input
nom.
AC 100-240V
Wide-range- input, see Fig. 5-1
AC input range
90-264Vac
100-120V range, continuous operation
85-90Vac
Short term or with output derating
264-300Vac <
0.5s
Input
frequency
nom.
50 – 60Hz
±6%
AC 100V
AC 120V
AC 230V
Input
current
typ.
1.5A
1.24A
0.68A
At 24V, 3.3A see Fig. 5-3
Power factor *
typ.
0.62
0.61
0.56
At 24V, 3.3A see Fig. 5-1
Crest factor **
typ.
3.1 3.2 4.0
At
24V,
3.3A
Start-up
delay
typ.
95ms 95ms 95ms
See
Fig.
5-2
Rise
time
typ.
18ms
29ms
56ms
0mF, 24V, 3.3A, see Fig. 5-2
typ.
35ms
52ms
52ms
3.3mF, 24V, 3.3A, see Fig. 5-2
Turn-on
overshoot
max.
400mV 400mV 400mV
See
Fig.
5-2
Turn-on
voltage
typ.
75Vac
75Vac
75Vac
Steady-state value, see Fig. 5-1
Shut-down
voltage
typ.
58Vac
58Vac
58Vac
Steady-state value, see Fig. 5-1
*
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**
The crest factor is the mathematical ratio of the peak value to the RMS value of the input current waveform
Fig. 5-1 Input voltage range
Fig. 5-2 Turn-on behavior, definitions
Tu
rn
-o
n
90
Rated
input range
max.
500ms
V
IN
P
OUT
58
300Vac
264
Shut
-dow
n
75
Start-up
delay
Rise
Time
O
ve
rs
hoot
- 5%
Output
Voltage
Intput
Voltage
Fig. 5-3 Input current vs. output load
Fig. 5-4 Power factor vs. output load
0.5
1.5
1.0
2.0
2.5
3.0 3.5A
0
0.3
0.6
0.9
1.2
1.5
1.8A
Output Current
Input
Current, typ.
(a) 100Vac
(b) 120Vac
(c) 230Vac
(a)
(b)
(c)
Power
Factor, typ.
0.5
1.0
1.5
2.0
3.5A
0.40
0.45
0.50
0.55
0.60
0.65
Output Current
2.5
3.0
(a) 100Vac
(b) 120Vac
(c) 230Vac
(a)