The Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 909

Bulletin 909 

Model N25 (SIN RA0912)
Early Suppression
Fast Response Sprinkler

Product Description

The Reliable Model N25 Early Suppression Fast Re-

sponse Sprinkler (ESFR/Quick Response Storage Sprin-
kler) is intended for use against severe fire challenges. 
This sprinkler is designed to respond quickly to growing 
fires and will deliver a heavy water discharge to “sup-
press”  rather than  “control.”

Note:

 The Model N25 ESFR sprinkler utilizes a levered 

fusible alloy solder link in either a 165°F (74°C) or a 
212°F (100°C) rating. FM Global considers this a “Quick 
Response” storage sprinkler for use per FM Data Sheet 
8-9.

The sprinkler has a Nominal K Factor of 25.2 (metric 

362) and will deliver approximately 98 gpm (371 L/min) 
of water at 15 psi (1 bar).

The smaller deflector and frame provide a broad, very 

symmetrical, hemispherical pattern capable of sup-
pressing fires between sprinklers in high storage height 
areas and at the same time retaining a high momentum 
central core to penetrate and suppress fires occurring 
directly beneath the sprinkler in low storage height ar-
eas.

The N25 ESFR sprinkler is also less susceptible to 

damage due to smaller deflector and frame design. The 
lighter N25 ESFR passed rough use and abuse test in 
the labs without plastic protectors.

Application and Installation

The Model N25 is an ESFR sprinkler is intended for 

installation in accordance with NFPA 13 and is a QR 
Storage Sprinkler for use in all FM Loss Prevention Data 
Sheets as well as approval of the Authority Having Ju-
risdiction.

The Model N25 ESFR sprinkler is designed for ceiling 

only sprinkler system with no in-rack sprinklers required. 
Protection of (but not limited to) most encapsulated or 
non-encapsulated (including cartoned unexpanded) 
plastics. Model N25 ESFR is also use for protection of 
cartoned exposed expanded plastics as well as some 
storage arrangements of rubber tires, rolled paper, and  
aerosols.

Model N25 ESFR Sprinkler

Design Criteria

General guidelines:

Sprinkler Position:

 Pendent, align frame arms with 

the pipe. Deflectors should be parallel with the ceil-
ing or roof.

System Type:

 Wet Pipe Systems Only

Maximum area of coverage:

 100 ft

2

 (9.3m

2

), greater 

coverage area are allowable in some cases.

Minimum area of coverage:

 64 ft

2

 (5.8m

2

)

Maximum slope ceiling:

 2/12 pitch (9.5°)

Maximum spacing:

 12 ft (3.7m) for building heights 

up to 30 ft (9.1m) and 10 feet (3.1m) for building 
heights greater than 30 ft (9.1m) 

Minimum spacing:

 8 feet (2.4m)

De

fl

 ector distance from walls:

 At least 4 inches 

(102mm) from walls, and no more than one-half the 
allowable distance permitted between sprinklers.

De

fl

 ector to Top of Storage:

 at least 36 in (914mm).

De

fl

 ector to ceiling Distance:

 6 - 18 in (152 - 

457mm).

Center Line of Thermal Sensing
Element To Ceiling Distance:

 4 - 17 in (101.6 - 

425mm).

Listings and Approvals 

1.  FM Approved as a quick response storage sprinkler.

Summary of Contents for N25

Page 1: ... Application and Installation The Model N25 is an ESFR sprinkler is intended for installation in accordance with NFPA 13 and is a QR Storage Sprinkler for use in all FM Loss Prevention Data Sheets as well as approval of the Authority Having Ju risdiction The Model N25 ESFR sprinkler is designed for ceiling only sprinkler system with no in rack sprinklers required Protection of but not limited to m...

Page 2: ...on Number SIN F C F C Ordinary Intermediate 165 212 74 100 Black White Uncolored White 100 150 38 66 FM FM RA0912 Material Data Frame Deflector Load Screw Lever Strut Link Assembly Cap Washer Kick Spring Brass Bronze Stainless Steel Stainless Steel Stainless Steel Beryllium Nickel Soldered Brass Beryllium Nickel Stainless Steel 2 Fig 1 ...

Page 3: ...PA 13 Chapter 12 Refer to FM 8 24 Rubber Tire Storage Refer to NFPA 13 Chapter 18 Refer to FM 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Chapter 19 Refer to FM 8 21 Flammable Liquid Storage Refer to standard Refer to NFPA 30 Refer to FM 7 29 Aerosol Storage Refer to the standard Refer to NFPA 30B Refer to FM 7 31 Automotive Components In Portable Racks Control mode only refer ...

Page 4: ...al cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non operation Once operated automatic sprinklers cannot be reassem bled and reused New sprinklers of the same size type and temperature rating must be installed A cabinet of re placement sprinklers should be provided for this purpose Model N25 ESFR Sprinkler Specification S...

Reviews: