Manufactured by:  Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446

Product
Description

Omega  HEC-12EC

Extended  Coverage Quick Response
(16'x18') 

(4.9m x 5.5m)

Extended  Coverage (16'x20')

(4.9m x 6.1m)

Horizontal Sidewall Automatic Sprinkler

1/2"

(12.7mm)

Orifice
Horizontal
Sidewall
Automatic
Sprinkler

Model:  HEC-12EC

Style:  Horizontal Sidewall

Orifice Size:  1/2" 

(12.7 mm)

K Factor:  5.6 

(80.1 metric)

Thread Size:  1/2" 

(15 mm)

 N.P.T.

Temperature Rating:

145

°

F/63

°

C - Extended Coverage

Quick Response (ECQR)

160

°

F/71

°

C - Extended Coverage

Quick Response, Extended
Coverage (ECQR) (EC)

Approvals: U.L., U.L.C., MEA

(Cal. No. 375-75-SA)

Maximum Working Pressure:
175 psi 

(12.1 bar)

Factory Hydro Test: 100% at
500 psi 

(34.5 bar)

Technical
Data

The Omega Model HEC-12EC
Sprinkler is the most versatile
horizontal sidewall sprinkler ever
produced.  It is a low profile,
aesthetically pleasing, wall mounted
sprinkler that operates five to six times
faster than a standard sprinkler. It
offers a high degree of protection for
human life and features a spray
pattern that has been shown to be
effective in the control or
extinguishment of fire.

The Model HEC-12EC carries two
separate Listings* by Underwriters
Laboratories for use as:

1.   An Extended Coverage Quick

Response Sprinkler that qualifies
for installation at  4"-12"

(101.6mm -

304.8mm)

 below the ceiling in light

hazard occupancies in accordance
with current NFPA 13 Standards
(for up to 16' x 18'

(4.9 mm - 5.5 mm)

coverages).

2.   An Extended Coverage Sprinkler

that qualifies for installation 4"-
6"

(101.6mm - 152.4mm)

  below the

ceiling in light hazard occupancies
in accordance with current NFPA
13 Standards (for up to 16' x 20'

(4.9

mm - 6.1 mm)

 coverages).

The Model HEC-12EC is available in
two standard finishes, brass and
chrome plated.  Its mating escutcheon
plate is available in three standard
finishes, brass, chrome plated, and

Standard Finishes:

Sprinkler:  brass, chrome plated

and white painted

Escutcheon:  brass, chrome

plated and white
painted

Length: 2 3/8" 

(60.3 mm)

Width:

1 3/8" 

(34.9 mm)

Weight: 4.5 oz. 

(127.6 g)

white, with additional special finishes
available upon request.

Operation:  A fusible alloy pellet is
compressed with a bearing disc into
a copper housing by a ball plunger.
Heat is absorbed by the heat
collecting fins and conducted to the
alloy pellet.  At the rated temperature
the alloy melts, causing the ball
plunger to drop, freeing balls from
the retaining groove.  This movement
allows system water pressure to
force the orifice sealing mechanism
and deflector assembly open.  Water
is then discharged in a designed flow
pattern.

HEC-12EC

2-98

*For specific listing requirements see the appropriate
information contained in this brochure.

No. 2-14.0

OBSOLETE

Содержание CENTRAL Omega HEC-12EC

Страница 1: ...onse Sprinkler that qualifies for installation at 4 12 101 6mm 304 8mm below the ceiling in light hazard occupancies in accordance with current NFPA 13 Standards for up to 16 x 18 4 9 mm 5 5 mm coverages 2 An Extended Coverage Sprinkler that qualifies for installation 4 6 101 6mm 152 4mm below the ceiling in light hazard occupancies in accordance with current NFPA 13 Standards for up to 16 x 20 4 ...

Страница 2: ... 4 57 4mm Dia Max 2 50 8mm Dia Min Finished Wall Line A 1 2 1 1 8 25 4 3 2mm Note Use this flange for field installation Use Central s Omega HEC Sprinkler Wrench DO NOT WRENCH DEFLECTOR See Table on Page 3 Escutcheon 12 7mm Omega HEC Sprinkler Wrench Figure 1 Omega HEC 12EC Horizontal Sidewall O B S O L E T E ...

Страница 3: ... 13 Standards Deviations from these requirements and standards or any alteration to the sprinkler itself will void any warranty made by Central Sprinkler Company In addition installation must also meet local government provisions codes and standards as applicable The system piping must be properly sized to insure the minimum required flow rate from the sprinkler Prior to installation check for pro...

Страница 4: ...ified inspection service Length of time between such inspections can vary due to accessibility ambient atmosphere water supply and site activity Do not attempt to re assemble or otherwise reuse a sprinkler that has operated Replace any sprinkler exhibiting corrosion or damage always use new sprinklers of the same type and temperature rating as replacements Because the discharge pattern is critical...

Отзывы: