Installation, user and maintenance manual
– GAHP-A
33
LPG may cause corrosion; piping and fitting materials must be resistant to this
corrosion.
Vertical gas pipes must be equipped with a siphon and provided with a drain for the con-
densate that may form inside the pipe during cold periods. It may also be necessary to
insulate the gas pipe to prevent the formation of excessive condensate.
In any case, provide an isolation valve (ball valve) on the gas supply line, to isolate the
appliance when required.
table 5�2 – Network gas pressure
e3-Gs; e3-Ws; e3-A; GAHP-Gs; GAHP-Ws; GAHP-A
Gas supply pressure
Product categories
Countries of destination
G20 [mbar]
G25 [mbar]
G30 [mbar]
G31 [mbar]
G25�1
[mbar]
G27 [mbar] G2,350 [mbar]
II
2H3B/P
AL, BG, CY, CZ, DK, EE, FI, GR,
HR, IT, LT, MK, NO, RO, SE,
SI, SK, TR
20
30
30
AT, CH
20
50
50
II
2H3P
AL, BG, CZ, ES, GB, HR, IE, IT,
LT, MK, PT, SI, SK, TR
20
37
RO
20
30
II
2ELL3B/P
DE
20
20
50
50
II
2Esi3P
FR
20
25
37
II
2HS3B/P
HU
25
30
30
25
II
2E3P
LU
20
50
II
2L3B/P
NL
25
50
50
II
2E3B/P
PL
20
37
37
II
2ELwLs3B/P
20
37
37
20
13
II
2ELwLs3P
20
37
20
13
I
2E(R)B ; I3P
BE
20
25
37
I
3P
IS
30
I
2H
LV
20
I
3B/P
MT
30
30
I
3B
30
For data regarding hourly fuel consumption of the appliance, refer to Table 3.1 GAHP-A LT
technical data
→
11 or Table 3.2 GAHP-A HT technical data
→
13.
5�5
CondensAte dIsCHARGe
The fumes condensate outlet is on the left of the appliance.
The distance L between the coupling C and the base may not exceed 110 mm.
The condensate discharge corrugated pipe, coming out from the side of the un-
1.
derbase left support, must be connected to a proper discharge header.
The connection between the pipe and the manifold must remain visible.
2.