50
figure 6�10 – Electrical wiring diagram
Connection cable CAN BUS to electronic board: detail A case "terminal node", detail B case "intermediate node"
LeGend
SCH
electronic board
GND
Common data
L
Data signal LOW
H
Data signal HIGH
J1
Jumper CAN-BUS in board
A
Detail case "terminal node" (3 wires;
J1=jumper "closed")
B
Detail case "intermediate node" (6
wires; J1=jumper "open")
P8
Port can/connector
After finished with all the above operations, close the electrical panel and refit the
8.
front panel of the appliance.
How to connect the CAn BUs cable to the Comfort Control Panel
The CAN bus cable is connected to the specific orange connector (P8) supplied with the
CCP in a bag.
Before working on the Comfort Control Panel, make sure that it is off.
The CCP, like the controller on the appliance, has jumpers that must be moved so that it
can be configured as an intermediate or terminal node. The position of the jumpers on
a new CCP is CLOSED.
To connect the CAN bus cable to a CCP:
You will need: the Comfort Control Panel not powered up.
Open the Comfort Control Panel’s electrical panel with the handle on its left.
1.
Depending on the type of node being configured, set the CCI’s jumpers J21 as
2.
shown in detail "A" or detail "B" in Figure 6.12 Connection of CCI to CAN-BUS net-
work
→
52. If necessary, open the CCI’s back panel (4 screws); after jumpers J21
have been correctly positioned, close the cover again and retighten the 4 bolts.
Cut a length of cable long enough to allow installing it without kinking.
3.
Remove the sheath for a length of approximately 70-80 mm, taking care not to cut
4.
the shielding (metallic shield and/or aluminium sheet and, if present, the bare con-
nector in contact with the shield) and wires contained inside.
Roll the shielding and connect it to a 4-mm eyelet terminal, as illustrated in Figure
5.
6.11 Connection from CAN BUS to connector P8
→
51, details C and D. Now pro-
ceed as follows: