78
9
oPeRAtInG Codes/tRoUBLesHootInG
9�1
oVeRVIeW And oPeRAtInG Codes/tRoUBLesHootInG
table 9�1 – TABLE OF OPERATING CODES generated by the S61 electronic board (firmware version 3.024)
CODES
DESCRIPTION
TRIP CONDITIONS
RESET METHOD
E 400
FAULT ON RESET CIRCUIT OF FLAME
CONTROL UNIT
Fault on reset circuit of flame control unit.
Contact authorised Technical Assistance.
u 401
GENERATOR LIMIT TEMPERATURE
THERMOSTAT
High temperature detected by limit thermostat
on body of generator
Acknowledge the thermostat manually: reset will be automatic as
soon as fault condition is over.
E 401
GENERATOR LIMIT TEMPERATURE
THERMOSTAT
u_01 code active for 1 hour, or u_01 code
generated 3 times in 2 hours of operation.
Contact authorised Technical Assistance.
u 402
FUMES THERMOSTAT
High temperature detected by exhaust fumes
thermostat
Acknowledge the thermostat manually: reset will be automatic as
soon as fault condition is over.
E 402
FUMES THERMOSTAT
u_02 code active for 1 hour, or u_02 code
generated 3 times in 2 hours of operation.
Contact authorised Technical Assistance.
E 405
HIGH AMBIENT TEMPERATURE
HIGH temperature detected by ambient
temperature sensor.
Reset occurs automatically when the condition that generated the
code ceases.
u 406
LOW AMBIENT TEMPERATURE
LOW temperature detected by ambient
temperature sensor.
Reset occurs automatically when the cause ceases or when the unit
is switched off.
u 407
HIGH CONDENSER INLET
TEMPERATURE
Temperature measured by condenser inlet sensor,
fumes sensor or generator fin sensor HIGH.
Reset occurs automatically when the condition that generated the
code ceases.
E 407
HIGH CONDENSER INLET
TEMPERATURE
u_07 code active for 1 hour, or u_07 code
generated 12 times in 2 hours of operation.
Carry out appropriate checks. Reset may be performed from the
controller (or from the S61 board via menu 2, parameter 21). If the
code persists, contact authorised Technical Assistance.
E 408
FLAME CONTROL UNIT ERROR
E_12 on unit and condenser inlet temperature
increasing by over 10 °C within 1 hour.
Carry out appropriate checks. Reset may be performed from the
controller (or from the S61 board via menu 2, parameter 21). If the
code persists, contact authorised Technical Assistance.
u 410
INSUFFICIENT HOT WATER FLOW
Insufficient water flow (the circulator is on and
the flowmeter measure a low water flow).
Reset occurs automatically when correct water flow is restored.
E 410
INSUFFICIENT HOT WATER FLOW
u_10 code is repeated, or code u_10 is active for
1 hour.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 411
INSUFFICIENT ROTATION OF OIL
PRESSURE PUMP
Insufficient rotation of oil pressure pump.
Reset occurs automatically 20 minutes after the Code is generated.
E 411
INSUFFICIENT ROTATION OF OIL
PRESSURE PUMP
u_11 code generated twice in 2 hours of
operation.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 412
FLAME CONTROL UNIT ARREST
Failure to ignite burner.
Reset occurs automatically when the solenoid valve opens again
(new ignition attempt), or if the code persists for 5 minutes.
E 412
FLAME CONTROL UNIT ARREST
Flame arrest signal.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 20). If the code persists, contact authorised
Technical Assistance.
E 416
HOT OUTLET WATER TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on outlet hot
water temperature sensor.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 417
COLD INLET WATER TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on inlet water
temperature sensor.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 420
CONDENSER INLET TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on condenser
inlet temperature sensor.
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 422
WATER FLOWMETER FAULT
Water flowmeter fault
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 423
AIR/GAS MIXTURE SENSOR FAULT
Air gas mixture sensor fault
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 424
FUMES TEMPERATURE SENSOR
FAULT
Fumes temperature sensor fault
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 425
CONDENSATE DISCHARGE
CLOGGED
Condensate discharge clogged
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 426
GENERATOR FIN TEMPERATURE
SENSOR
Generator fin temperature sensor
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
E 428
GAS SOLENOID VALVE EXCITED
DURING FLAME CONTROLLER
ARREST
The flame controller is arrested (E_12) but the gas
solenoid valve is excited. In this case the flame
controller is de-excited (E_12 resets).
Reset may be performed from the controller (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Technical Assistance.
u 429
GAS SOLENOID VALVE WITHOUT
ELECTRICAL POWER
Gas solenoid valve is off for 5 seconds (with
central flame control unit on).
Reset occurs automatically if the gas solenoid valve switches on
again within 10 minutes (with central flame control unit on).
E 429
GAS SOLENOID VALVE WITHOUT
ELECTRICAL POWER
Code u_29 is active for more than 10 minutes
(with flame controller unit on).
Carry out appropriate checks. Reset may be performed from the
controller (or from the S61 board via menu 2, parameter 21). If the
code persists, contact authorised Technical Assistance.
u 436
BLOWER FAULT
Blower fault
Reset occurs automatically 20 minutes after the operating code is
generated.