6. MODBUS COMMUNICATION PROTOCOL
IMR01J08-E1
46
Continued from the previous page.
(Attribute
RO: Read only, R/W: Read and Write)
Resister
address
Name
Hexa-
decimal Decimal
Attrib-
ute
Data range
Factory set
value
Alarm 1 differential
gap
003A 58
Note 1 0 (0.0) to Span
Temperature
input:
2 (2.0)
°
C [
°
F]
Voltage/current
inputs:
0.2 % of span
Alarm 1 process
abnormality action
selection
003B 59
Note 1 0: Normal processing
1: Turn the alarm output ON
Alarm 1 not
provided: 0
Alarm 1
provided: 1
Alarm 1 interlock
003C 60
Note 1 0: Without alarm interlock
1: With alarm interlock
0
Alarm 1 timer unit
003D 61
Note 1 0 to 60 (sec)
0
Alarm 2 type
selection
003E 62
Note 1 0: Alarm not provided
1: SV high alarm
2: SV low alarm
3: Process high alarm
4: Process low alarm
5: Deviation high alarm
6: Deviation low alarm
7: Deviation high/low alarm
8: Band alarm
Note 2
Alarm 2 hold
action
003F 63
Note 1 0: Without alarm hold action
1: Effective when the power is turned
on
2: Effective when the power is turned
on or the SV is changed
Note 2
Alarm 2 differential
gap
0040 64
Note 1 0 (0.0) to Span
Temperature
input:
2 (2.0)
°
C [
°
F]
Voltage/current
inputs:
0.2 % of span
Alarm 2 process
abnormality action
selection
0041 65
Note 1 0: Normal processing
1: Turn the alarm output ON
Alarm 2 not
provided: 0
Alarm 2
provided: 1
Alarm 2 interlock
0042 66
Note 1 0: Without alarm interlock
1: With alarm interlock
0
Note 1: Attribute varies depending on the Engineering mode (Resister address: 0030H) setting.
Note 2: Factory set value varies depending on the instrument specification.
Continued on the next page.