5. RKC COMMUNICATION PROTOCOL
IMR01J08-E1
27
Continued from the previous page.
(Attribute
RO: Read only, R/W: Read and Write)
Name Iden-
tifier
Data range
Factory set
value
Attribute
Display unit selection
PU
0:
°
C
1:
°
F
0 Note
1
Decimal point
position
XU
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
Note 2
Note 1
Setting limiter [high]
XV
Setting limiter [low] to Maximum value
of the selected input range
Temperature
input:
Maximum value
of the selected
input range
Voltage/current
inputs: 100.0
Note 1
Setting limiter [low]
XW
Minimum value of the selected input
range to Setting limiter [high]
Temperature
input:
Minimum value
of the selected
input range
Voltage/current
inputs: 0.0
Note 1
Output logic operation
selection
LO
See Table 1 (P.30)
Note 2
Note 1
Alarm 1 type selection
XA
0: Alarm not provided
1: SV high alarm
2: SV low alarm
3: Process high alarm
4: Process low alarm
5: Deviation high alarm
6: Deviation low alarm
7: Deviation high/low alarm
8: Band alarm
Note 2
Note 1
Alarm 1 hold action
WA
0: Without alarm hold action
1: Effective when the power is turned
on
2: Effective when the power is turned
on or the SV is changed
Note 2
Note 1
Note 1: Attribute varies depending on the Engineering mode (Identifier: IO) setting.
Note 2: Factory set value varies depending on the instrument specification.
Continued on the next page.