6. MODBUS COMMUNICATION PROTOCOL
IMR01J08-E1
45
Continued from the previous page.
(Attribute
RO: Read only, R/W: Read and Write)
Resister
address
Name
Hexa-
decimal Decimal
Attrib-
ute
Data range
Factory set
value
Display unit
selection
0033 51
Note 1 0:
°
C
1:
°
F
0
Decimal point
position
0034 52
Note 1 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
Note 2
Setting limiter
[high]
0035 53
Note 1 Setting limiter [low] to Maximum
value of the selected input range
Temperature
input:
Maximum value
of the selected
input range
Voltage/current
inputs: 100.0
Setting limiter
[low]
0036 54
Note 1 Minimum value of the selected input
range to Setting limiter [high]
Temperature
input:
Minimum value
of the selected
input range
Voltage/current
inputs: 0.0
Output logic
operation selection
0037 55
Note 1 See Table 1 (P.48)
Note 2
Alarm 1 type
selection
0038 56
Note 1 0: Alarm not provided
1: SV high alarm
2: SV low alarm
3: Process high alarm
4: Process low alarm
5: Deviation high alarm
6: Deviation low alarm
7: Deviation high/low alarm
8: Band alarm
Note 2
Alarm 1 hold
action
0039 57
Note 1 0: Without alarm hold action
1: Effective when the power is turned
on
2: Effective when the power is turned
on or the SV is changed
Note 2
Note 1: Attribute varies depending on the Engineering mode (Resister address: 0030H) setting.
Note 2: Factory set value varies depending on the instrument specification.
Continued on the next page.