6. MODBUS COMMUNICATION PROTOCOL
IMR01J08-E1
42
Continued from the previous page.
(Attribute
RO: Read only, R/W: Read and Write)
Resister
address
Name
Hexa-
decimal Decimal
Attrib-
ute
Data range
Factory set
value
Alarm 1 timer
000D 13
R/W
1
0 to 9999
Alarm 2 set value
000E 14
R/W
2
Process alarm, SV alarm:
Same as input range
Deviation alarm:
−
Span to +Span
However, within
−
1999 to +9999 digits
Temperature
input: 50 or 50.0
Voltage/current
inputs: 5.0
Alarm 2 timer
000F 15
R/W
3
0 to 9999
PV bias
0010 16
R/W
−
Span to +Span
However, within
−
1999 to +9999 digits
Temperature
input: 0 or 0.0
Voltage/current
inputs: 0.0
PV ratio
0011 17
R/W 0.500 to 1.500
1.000
Digital filter
0012 18
R/W 0 to 100 seconds (0: OFF)
0
Analog output
selection
0013 19
Note 1 0: Measured value (PV)
1: Set value (SV)
2: Deviation
0
Analog output scale
high
4
0014 20
Measured value (PV), Set value (SV):
Same as input range
Deviation:
−
Span to +Span
Temperature
input:
Input range
(high limit)
Voltage/current
inputs: 100.0
Analog output scale
low
4
0015 21
Temperature
input:
Input range
(low limit)
Voltage/current
inputs: 0.0
1
If Alarm 1 is not provided or Alarm 1 timer unit is set to 0, the attribute becomes RO.
2
If Alarm 2 is not provided, the attribute becomes RO.
3
If Alarm 2 is not provided or Alarm 2 timer unit is set to 0, the attribute becomes RO.
4
The setting range is from
−
1999 to +9999 regardless of the position of the decimal point.
Note 1 Set the attribute to R/W (Read and Write) for OUT1 when OUT1 is used as transmission output.
Set the attribute to RO (Read only) for OUT1 when OUT1 is not used as transmission output.
Continued on the next page.