2-16 Riverstone Networks RS 8000/8600 Switch Router Getting Started Guide
Hardware Overview
Introduction
2.4.6
DC Power Supply
The RS DC power supply delivers 3.3, 5, and 12 volts DC to the RS’s Control Module(s), fan modules, and other
components. A single DC power supply provides enough current to operate a fully configured chassis.
Figure 2-6
shows the front view of an RS 8000 DC power supply.
Figure 2-6 Front view of an RS 8000 DC power supply
The RS 8000 DC power supply has a three-terminal wiring block on the front panel, consisting of a positive (+)
terminal, negative (-) terminal and a safety ground. The DC supply is designed to be powered by a 48 Volt DC source.
Use 12-gauge to 14-gauge wire to connect the 48-Volt source to the RS 8600 DC power supply. Use 12-gauge to
14-gauge wire for the safety ground.
Figure 2-7
shows the front view of an RS 8600 DC Power Supply.
Figure 2-7 Front view of an RS 8600 DC power supply
The RS 8600 DC power supply has a five-terminal wiring block on the front panel, consisting of two positive (+)
terminal, two negative (-) terminal and a safety ground. The DC supply is designed to be powered by a 48-Volt DC
source.
G80-PDC
PWR
SN
!
To be installed in a restricted
access area in accordance
with the NEC or authority
having jurisdiction.
See manual for installation
instructions.
48/60V
14A MAX
PWR
G86-PDC
SN
48/60V
27A MAX
!
To be installed in a restricted
access area in accordance
with the NEC or authority
having jurisdiction.
See manual for installation
instructions.