13 Further technical information
EN
20 kW devices 3311.600/700/800/900
Cooling output, sensible [kW]
15
15
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
17
18
Return temperature [°C]
20
21
21.5
22
22
22.5
23
Water volume [l/min]
23
25
28
30
33
38
42
Volumetric airflow [m
3
/h]
3500
3500
3500
3500
3500
3500
3500
Air outlet from LCP Hybrid [°C]
24
24
24
24
24
24
24
Air inlet to LCP Hybrid [°C]
36
36
36
36
36
36
36
T air [K]
12
12
12
12
12
12
12
Tab. 41: Cooling output at partial load and a
T air of 12 K
Cooling output, sensible [kW]
15
15
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
17
18
Return temperature [°C]
21
21.5
22
22
22
23
23.5
Water volume [l/min]
24
26
28
30
34
38
38
Volumetric airflow [m
3
/h]
3000
3000
3000
3000
3000
3000
3000
Air outlet from LCP Hybrid [°C]
24
24
24
24
24
24
24
Air inlet to LCP Hybrid [°C]
39
39
39
39
39
39
39
T air [K]
15
15
15
15
15
15
15
Tab. 42: Cooling output at partial load and a
T air of 15 K
Cooling output, sensible [kW]
18
18
18
18
18
18
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
20
20
20
21
21
22
Water volume [l/min]
30
34
36
40
46
55
Volumetric airflow [m
3
/h]
4200
4200
4200
4200
4200
4200
Air outlet from LCP Hybrid [°C]
24
24
24
24
24
24
Air inlet to LCP Hybrid [°C]
36
36
36
36
36
36
T air [K]
12
12
12
12
12
12
Tab. 43: Cooling output at full load and a
T air of 12 K
Cooling output, sensible [kW]
20
20
20
20
20
20
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
20
20
21
21
21
18
Water volume [l/min]
40
44
46
54
60
75
Volumetric airflow [m
3
/h]
4500
4500
4500
4500
4500
4500
Air outlet from LCP Hybrid [°C]
24
24
24
24
24
24
Tab. 44: Cooling output at full load and a
T air of 15 K