13 Further technical information
EN
34
Rittal Liquid Cooling Package
20 kW devices 3311.600/700/800/900
Air outlet from LCP Hybrid [°C]
21
21
21
21
21
Air inlet to LCP Hybrid [°C]
36
36
36
36
36
T air [K]
15
15
15
15
15
Cooling output, sensible [kW]
10
10
10
10
10
Tab. 16: Cooling output at full load and a
T air of 15 K
Cooling output, sensible [kW]
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
Return temperature [°C]
18.5
19
19
19
20
Water volume [l/min]
32
36
42
50
60
Volumetric airflow [m
3
/h]
3600
3600
3800
3800
3800
Air outlet from LCP Hybrid [°C]
21
21
21
21
21
Air inlet to LCP Hybrid [°C]
33
33
33
33
33
T air [K]
12
12
12
12
12
Tab. 17: Cooling output at partial load and a
T air of 12 K
Cooling output, sensible [kW]
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
Return temperature [°C]
19
19
19
20
20
Water volume [l/min]
32
36
43
48
60
Volumetric airflow [m
3
/h]
3200
3200
3200
3200
3200
Air outlet from LCP Hybrid [°C]
21
21
21
21
21
Air inlet to LCP Hybrid [°C]
36
36
36
36
36
T air [K]
15
15
15
15
15
Tab. 18: Cooling output at partial load and a
T air of 15 K
Cooling output, sensible [kW]
20
20
20
20
Inlet temperature [°C]
12
13
14
15
Return temperature [°C]
17.5
18
18
19
Water volume [l/min]
50
55
60
75
Volumetric airflow [m
3
/h]
4500
4800
4800
4800
Air outlet from LCP Hybrid [°C]
21
21
21
21
Air inlet to LCP Hybrid [°C]
33
33
33
33
T air [K]
12
12
12
12
Tab. 19: Cooling output at full load and a
T air of 12 K