13 Further technical information
EN
38
Rittal Liquid Cooling Package
20 kW devices 3311.600/700/800/900
Volumetric airflow [m
3
/h]
1000
1000
1000
1000
1000
1000
1000
1000
1000
Air outlet from LCP Hybrid [°C]
23
23
23
23
23
23
23
23
23
Air inlet to LCP Hybrid [°C]
38
38
38
38
38
38
38
38
38
T air [K]
15
15
15
15
15
15
15
15
15
Cooling output, sensible [kW]
10
10
10
10
10
Inlet temperature [°C]
12
13
14
15
16
Return temperature [°C]
18.5
19
19.5
19
19
Water volume [l/min]
21
23
25
46
47
Volumetric airflow [m
3
/h]
2400
2400
2400
2900
2900
Air outlet from LCP Hybrid [°C]
23
23
23
23
23
Air inlet to LCP Hybrid [°C]
35
35
35
35
35
T air [K]
12
12
12
12
12
Tab. 31: Cooling output at full load and a
T air of 12 K
Cooling output, sensible [kW]
10
10
10
10
10
Inlet temperature [°C]
12
13
14
15
16
Return temperature [°C]
19
19
20
19
20
Water volume [l/min]
21
23
25
46
50
Volumetric airflow [m
3
/h]
2000
2000
2000
2600
2600
Air outlet from LCP Hybrid [°C]
23
23
23
23
23
Air inlet to LCP Hybrid [°C]
38
38
38
38
38
T air [K]
15
15
15
15
15
Tab. 32: Cooling output at full load and a
T air of 15 K
Cooling output, sensible [kW]
5
5
5
5
5
5
5
5
5
Tab. 30: Cooling output at partial load and a
T air of 15 K
Cooling output, sensible [kW]
15
15
15
15
15
15
Inlet temperature [°C]
12
13
14
15
16
17
Return temperature [°C]
19
19.5
20
20
20.5
21
Water volume [l/min]
30
32
34
38
46
58
Volumetric airflow [m
3
/h]
3700
3700
3700
3700
3700
3700
Air outlet from LCP Hybrid [°C]
23
23
23
23
23
23
Air inlet to LCP Hybrid [°C]
35
35
35
35
35
35
T air [K]
12
12
12
12
12
12
Tab. 33: Cooling output at partial load and a
T air of 12 K