Environmental conditions
0
-20 to +70 C
0
-40 to +85 C
0 .. 95 % RH (Non condensing)
3 minute (minimum)
Half Sine wave,Peak acceleration
30gn (300 m/s^2), duration 18 ms
10..150..10 Hz, 0.15mm amplitude
Operating temperature
Storage temperature
Relative humidity
Warm up time
Shock (As per
IEC 60068-2-27)
Vibration
10 per axis
Number of Sweep cycles
96mm x 96mm DIN 43718
92mm+0.8 X 92mm+0.8
Bezel Size
Panel cut out
Overall Depth
Dimensions
Enclosure
Enclosure front
IP 20
Enclosure back (Terminals)
4 kV RMS, 50Hz, 1 min
Input+Aux vs Surface
3.3 kV RMS, 50Hz, 1 min
Input/Aux vs Remaining Circuit
IP 54
Isolation
High Voltage Test
2
Protective Class
59 mm without the Add-on Card
79 mm with Ehternet or Modbus Card
5kV for 1.2uSec
Impulse Voltage Withstand
2.2 kV RMS, 50Hz, 1 min
DI vs DI/Relay vs Relay
3.3 kV RMS, 50Hz, 1 min
DI/Relay/RS485/USB vs Remaining
Lexan 940 (polycarbonate), Flammability
Class V-0 acc. to Ul94, self extinguishing,
non dripping, free of halogen
Mechanical Housing
Conventional screw type terminal with indirect wire
terminals
Connection Element
2
2
4 mm solid or 2.5 mm stranded cable
Connection Terminal