TABLE 2.2 : Energy Pulse Rate Divisor
Pulse Duration 60 ms,100 ms or 200 ms
10
100
1000
1 per 10Whr
1 per 100Whr
1 per 1000Whr
1 per kWhr
1 per 10kWhr
1 per 100kWhr
1 per 1000kWhr
1 per MWhr
1 per 10MWhr
1 per 100MWhr
1 per 1000MWhr
Up to 3600 W
Up to 3600 W
Up to 3600 W
Up to 3600 kW
Up to 3600 kW
Up to 3600 kW
Up to 3600 kW
Above 3600 kW
up to 30000 kW
Above 3600 kW
up to 30000 kW
Above 3600 kW
up to 30000 kW
Above 3600 kW
up to 30000 kW
Divisor
1
Pulse
1 per Whr
System Power*
Up to 3600 W
Pulse rate
1.For Energy Output in Whr
Divisor
1
Pulse rate
Pulse
System Power*
1 per kWhr
1 per MWhr
Up to 3600 kW
Above 3600 kW
Divisor
1
Pulse rate
Pulse
1 per MWhr
Above options are also applicable for Apparent and Reactive Energy.
*Note:
1) System power = 3 x CT(Primary) x PT (Primary) L-N for 3 Phase 4 Wire
2) System power = Root3 x CT(Primary) x PT (Primary)L-L for 3 Phase 3 Wire
3) System power = CT(Primary) x PT(Primary)L-N for 1 Phase 2 Wire
2.For Energy Output in kWhr
3.For Energy Output in
MWhr
TABLE 2.1 : Continued...
26
27
28
29
30
31
32
Parameter
Number
Parameter
3P4W
3P 3W
1P 2W
Total Sys Apparent Energy
Total Active Energy L1
Total Active Energy L2
Total Active Energy L3
Total Reactive Energy L1
Total Reactive Energy L2
Total Reactive Energy L3
83