14
PARAMETERS, LOGICS AND SPECIAL FUNCTIONS
The following tables describe the individual functions available in the control unit.
PARAMETERS (
PAR
)
MENU
FUNCTION
MIN-MAX-(Default)
MEMO
TCA
Automatic ascent time of bollard 1 and bollard 2.
At the end of the set time the control unit commands the bollard ascent again.
3-240-(10s)
TM1
Bollard working time 1. Adjusts the maximum duration of the descent and ascent
manoeuvre of bollard 1.
It must be set about 4 seconds longer than the actual running time of the automatism.
1-90-(10s)
TM2
Bollard working time. Adjusts the maximum duration of the bollard descent and as-
cent manoeuvre 2.
It must be set about 4 seconds longer than the actual running time of the automatism.
1-90-(10s)
BLC
Hold time, it commands an ascent manoeuvre for approx. 3 seconds
Value expressed in hours. The value 0 disables the function.
0-12-(2)
Aux1
Sets the operating mode of auxiliary output 1
0: Contact for connection of bollard status light (see AUX connection diagram).
Light on when the bollard is lowered.
Flashing light frequency 1 flash/second with bollard in descent.
Flashing light frequency 2 flash/second with bollard in ascent.
Warning light off with bollard raised.
1: AUX 1 contact closed only when bollard 1 is raised and open when the bollard is
lowered or moving.
2: Contact for connection of siren/alarm, closed during the ascent of the bollard 1,
see connection diagram Fig.6.
3: Output replicates the status of input LSC1
4: Output reverses the status of input LSC1
5: Light-buzzer board command output
0-5-(5)
Aux2
Sets the operating mode of auxiliary output 2
0: Contact for connection of bollard status light (see AUX connection diagram).
Light on when the bollard is lowered.
Flashing light frequency 1 flash/second with bollard in descent.
Flashing light frequency 2 flash/second with bollard in ascent.
Warning light off with bollard raised.
1: AUX 2 contact closed only when the bollard is raised and open when the bollard is
lowered or moving.
2: Contact for siren/alarm connection, closed during the ascent of the bollard, see
connection diagram Fig.6.
3: Output replicates the status of input LSC2
4: Output replicates the status of input LSO2
5: Light-buzzer board command output mod. CP.BL (fig.10)
0-5-(0)
LOGICS (
LOG
)
MENU
FUNCTION
ON-OFF-(Default)
MEMO
tca
Enables or disables the automatic ascent time.
(OFF)
IbL
Enables or disables the shared function.
On: shared function enabled. The transmitter P.P. pulse has no effect during the de-
scent phase.
Off: shared function disabled.
(OFF)
IbCA
Enables or disables PP commands from the transmitter during the TCA phase.
On: PP commands not enabled.
Off: PP commands enabled.
(OFF)
SCL
Enables or disables the rapid closing.
On: Fast ascent enabled. When the bollard is lowered or during the descent phase,
the photocell triggers automatic ascent after 3 seconds.
Activate only with TCA>0
Off: fast ascent disabled.
(OFF)
PP
Enables or disables the simultaneous operation of the bollards.
On: the input DOWN acts a PP input for bollard 1, the UP input acts as a PP input for
bollard 2
Off: the DOWN input operates both bollards during the descent, the UP input oper-
ates both bollards in closing (ascent)
(OFF)