65
PCB Adjustments for extended venting or high altitude
MODEL: EX11C
With power off, remove front cover and press the test button on the PCB. Use the
temperature arrows on the control panel to set as follows
(See the previous slide for an illustration)
NG
For installations from 0-
2000’ above sea level
with a vent length of 0 to 7 ft
Set code to A1*
with a vent length of 7 to 13 ft
Set code to A5
For installations from 2001-
5200’ above sea level
with a vent length of 0 to 7 ft
Set code to A2
with a vent length of 7 to 13 ft
Set code to A6
For installations from 5201-
7700’ above sea level
with a vent length of 0 to 7 ft
Set code to A3
with a vent length of 7 to 13 ft
Set code to A7
For installations from 7701-
10,200’ above sea level
with a vent length of 0 to 7 ft
Set code to A4
with a vent length of 7 to 13 ft
Set code to A8
LP
For installations from 0-
2000’ above sea level
with a vent length of 0 to 13 ft
Set code to L1* or L5
For installations from 2001-
5200’ above sea level
with a vent length of 0 to 13 ft
Set code to L2 or L6
For installations from 5201-
7700’ above sea level
with a vent length of 0 to 13 ft
Set code to L3 or L7
For installations from 7701-
10,200’ above sea level
with a vent length of 0 to 13 ft
Set code to L4or L8
*default setting
Summary of Contents for Energysaver ES38
Page 1: ...Rinnai ENERGYSAVER Direct Vent Wall Furnace Installation Fundamentals ...
Page 30: ...30 View of Properly Installed Unit ...
Page 50: ...50 Vent Termination OUTSIDE VIEW OF CORRECTLY INSTALLED TERMINATION ...
Page 60: ...60 Extended Venting And High Altitude Installation Procedures ...
Page 74: ...74 Decorative Covers For Vent Extension Kits ...