3PH Auxiliary Relay Box OIM

The 3-phase auxiliary relay box is used in conjunction with Rinnai commercial heat pump and electric tank and 

operates by receiving “close” signal from the heat pump.
Depending on the installation of heat pump hot water system, a 3-phase auxiliary relay box (i.e. auxiliary booster 

control box) may be supplied for supplementing heat at low ambient temperature. Terminals “3” and “4” from the 

heat pump provide a power free signal to control the auxiliary booster (as shown below). Use a minimum 0.75mm

2

 

two-core cable (provided by installer) to wire to heat pump terminals.
The auxiliary booster has been interlocked with the heat pump to only operate under low ambient or fault conditions.

• 

When ambient temperature falls below 5°C, auxiliary booster is activated. The auxiliary booster will operate 

until the set point reaches. Auxiliary booster will remain active until the ambient temperature reaches above 

7°C. Heat pump and auxiliary booster may work simultaneously.

• 

When ambient temperature falls below 0°C, heat pump is deactivated. Heat pump won’t activate until the 

ambient temperature reaches above 2°C. Only the auxiliary booster will operate until the set point reaches.

• 

When heap pump is in fault, auxiliary booster will operate instead of the heat pump until the set point 

reaches. Auxiliary booster will remain active until the heat pump fault is cleared.

SPECIFICATIONS

CHP3PH

Power Supply

AC415V~50Hz

Dimensions (mm)

290 (H) ×240 (W) ×150 (D)

Net Weight (kg)

4

Colour

Grey

Material

ABS

Ingress Protection Rating

IP44

MAIN POWER CONNECTION

WARNING

The premises wiring to the heater 

MUST

 be capable of withstanding the appliance load. Refer to 

the table “Specifications” on page 4 for load details.

All electrical connections and wiring 

MUST

 be installed, maintained and removed by authorised 

persons in accordance with AS/NZS 3000, and all other relevant local regulations and municipal 

building codes including OH&S requirements.
Disconnect all power prior to installation and commissioning.

Tank Sensor

Auxiliary Booster 

Primary Pump

BASIC OPERATION

Summary of Contents for CHP3PHAUX

Page 1: ...3HP Auxiliary Relay Box Operation Installation Manual MODEL CHP3PHAUX ...

Page 2: ...tallation read this manual thoroughly and gain a full understanding of the appliance to ensure safe and correct use IMPORTANT NOTICE FOR INSTALLERS Please leave these instructions with the end user after commissioning of the system and alert the end user of the content sections Warnings and Periodic Inspection and Maintenance This appliance must be installed in accordance with Manufacturer s Insta...

Page 3: ...s full of water NEVER use a flammable spray such as hair spray paint etc near this unit as this may cause a fire At the end of the service life of the heat pump water heater and prior to being disposed of a person qualified with refrigerant handling must recover the refrigerant from the system The refrigerant must not be vented to atmosphere Please call our National Help Line to arrange for an ins...

Page 4: ...7 C Heat pump and auxiliary booster may work simultaneously When ambient temperature falls below 0 C heat pump is deactivated Heat pump won t activate until the ambient temperature reaches above 2 C Only the auxiliary booster will operate until the set point reaches When heap pump is in fault auxiliary booster will operate instead of the heat pump until the set point reaches Auxiliary booster will...

Page 5: ...elect suitable cable size according to the electric element capacity of the tank Normally each 3 phase auxiliary relay box works with one electric tank AUXILIARY BOOSTER SIGNAL Wire terminals 3 and 4 to heat pump with a minimum 0 75mm2 two core cable provided by installer The cable length should be less than 10 metres POWER SUPPLY TO ELECTRIC TANK Connect all active neutral and earth wires directl...

Page 6: ...Rinnai 6 3PH Auxiliary Relay Box OIM ELECTRICAL DIAGRAM WIRING DIAGRAMS WIRING DIAGRAMS ...

Page 7: ...NO MAIN POWER SUPPLY 415V 50Hz SUPPLY TO TANK 415V 50Hz N L1 L2 L3 N GLAND MAIN ISOLATOR 415V 50Hz Auxiliary Contactor Auxiliary Contactor Auxiliary Contactor Electric Tank Electric Tank Electric Tank CHP3PHAUX CHP3PHAUX if provided CHP3PHAUX if provided TO HEAT PUMP TERMINAL 3 4 WIRING DIAGRAMS ...

Page 8: ...Tel 1800 000 340 Cost of a local call may be higher from a mobile phone National calls from public phones in Australia are free For further information visit www rinnai com au or email enquiry rinnai com au Rinnai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your Rinnai appliance If your appliance requires service please call o...

Reviews: