Operation, indications, diagnostic
8.4
Manual reset
Tab. AC
Press contemporaneously
and
for >1 second (Escape) to start the manual reset process. The
parameter
PrC
appears.
Display:
PrC
Press
and
for the parameter
rSt
.
Display:
rSt
run
appears during the download (restore process) of the program sequence.
At the end of the reset process, the unit is automatically in a lockout position (LOC 138) and
need to be released in order to work!
After 2 minutes, the unit passes to
Loc 138
At the end of the reset process, the unit is automatically in a lockout position (LOC 138) and
need to be released in order to work!
Press
for >1 second to release the unit.
Display:
OFF
-
and
+
> 1s
-
+
-
or
+
-
+
nfo
1..3 s
Alternatively
Alternatively
nfo
> 1s
nfo