Technical description of the burner
4.4
Technical data
Tab. B
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1,013 mbar - Altitude 0 m a.s.l.
(2)
Input gas pressure 8)(Fig. 3) with zero pressure in combustion chamber and at maximum burner output.
(3)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler, at maximum, average and minimum mod-
ulation output. The sound power is measured with the “Free Field” method, as per EN 15036, and according to an accurate “Accuracy: Category 3”
measurement, as described in EN ISO 3746.
4.5
Electrical data
Tab. C
Model
RX 500 S/PV
Type
852T3
Power
(1)
Delivery
(1)
min - max
min - max
kW
Mcal/h
80 - 490
69 - 422
Fuels
Natural gas: G20 (methane), G25 - LPG: (G31)
Supply pressure
(2)
mbar
17 - 65 (G20)
17- 65 (G31)
Gas valve input diameter
1”
1
/
2
Operation
–
Intermittent (min. 1 stop in 24 hours)
–
Modulating
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 55
Burner weight (without packaging)
kg
40
Noise level
(3)
Min.
Average
Max.
Sound pressure
dB(A)
53,7
62,2
70,5
Sound power
66,0
74,6
82,9
Model
RX 500 S/PV
Electrical power
1N ~ 230V +/-10% 50 Hz
Fan motor
rpm
V
kW
A
5700
230
0.75
3.6
Ignition transformer
V1 - V2
I1 - I2
230 V - 2 x 10 kV
0.3 A - 50 Hz 0.4 A
Absorbed electrical power
kW max
1.0
Protection level
IP 20