Start-up, calibration and operation of the burner
6.7
Switching off the burner
Press the button in position 0 to turn off the burner.
Disable the electrical supply. If the burner is turned off for long pe-
riods, close the manual gas gates.
6.8
Setting and safety parameters (programmed control box)
Tab. S
WARNING
Turning off the burner during post-purging, the
control box goes into lockout after a few seconds
(ERROR LOC:83).
Fig. 26
20138621
No.
Parameter
OEM-preset
Value
1
pre-purging time
30
Seconds
2
Safety time
3
Seconds
3
Flame stabilisation time
10
Seconds
4
Ignition attempts
3
Number
5
Post-purging time
0
Seconds
6
Pre-ignition time
3
Seconds
7
Attempts in the event of flame loss during operation
1
Number
8
Pre-post purging speed
5500
Rotations/min
9
Number of fan rotations: number of ignition load rotations
(P0)
1260
Rotations/min
10
Number of fan rotations: number of minimum load rotations
(P1)
800
Rotations/min
11
Number of fan rotations: number of nominal load rotations
(P2)
5700
Rotations/min
12
Limit number of ignition load rotations (P0) Minimum limit
1260
Rotations/min
13
Limit number of ignition load rotations (P0) Maximum limit
3500
Rotations/min
14
Limit number of minimum load rotations (P1) Minimum limit
800
Rotations/min
15
Limit number of minimum load rotations (P1) Maximum limit
2280
Rotations/min
16
Limit number of nominal load rotations (P2) Minimum limit
4020
Rotations/min
17
Limit number of nominal load rotations (P2) Maximum limit
5700
Rotations/min
18
Maximum number of fan rotations
5700
Rotations/min
19
Minimum load
nominal load ascending ramp
20
Seconds
20
Nominal load
minimum load descending ramp
20
Seconds
21
Pulses for rotation
3
Pulses/rotation
22
Analogue input (Return signal potentiometer ASZxx.3x)
0
-
0: 3-point input
1: 0-10 V
2: 0-135
3: 0-20 mA
4: 4-20 mA with lockout at I < 4 mA
5: 4-20 m