List of parameters PME71.901...)
Tab. AD
675.00
PWM: Min. PWM with pre-purging, SEC
Modification
0%
100%
1%
86%
SO
OEM
675.01
PWM: Max. PWM with ignition load, SEC
Modification
0%
100%
1%
34%
SO
OEM
676
Gain factor speed control
Reading only
0
255
1
112
SO
---
677
Integral action time speed control
Reading only
0s
37.485 s
0.147 s
0.441 s
SO
---
678
Derivative action time speed control
Reading only
0s
37.485 s
0.147 s
0s
SO
---
679.00
Constant time speed control PT1: Min. speed
interval from high flame to low flame
Modification
0s
37.485 s
0.147 s
6.027 s
SO
OEM
679.01
Constant time speed control PT1: Average
speed interval from high flame to low flame
Modification
0s
37.485 s
0.147 s
6.027 s
SO
OEM
679.02
Constant time speed control PT1: Upper speed
interval from high flame to low flame
Modification
0s
37.485 s
0.147 s
6.027 s
SO
OEM
679.03
Constant time speed control PT1: Total speed
interval from high flame to low flame
Modification
0s
37.485 s
0.147 s
6.027 s
SO
OEM
680.00
Speed interval for constant time PT1: Upper
speed interval threshold
Modification
800 rpm
9000 rpm
10 rpm
4000 rpm
SO
OEM
680.01
Speed interval for constant time PT1: Lower
speed interval threshold
Modification
800 rpm
9000 rpm
10 rpm
2000 rpm
SO
OEM
700
Error history
701.00
Current error: Error code
Reading only
2
255
1
---
mode
---
701.01
Current error: Start-up meter reading
Reading only
0
999999
1
---
mode
---
701.02
Current error: MMI phase
Reading only
---
---
---
---
mode
---
701.03
Current error: Power value
Reading only
0%
100%
1
---
mode
---
702.00
Error history former 1: Error code
Reading only
2
255
1
---
mode
---
702.01
Error history o1: Start-up meter reading
Reading only
0
999999
1
---
mode
---
702.02
Error history o1: MMI phase
Reading only
---
---
---
---
mode
---
702.03
Error history o1: Power value
Reading only
0%
100%
1
---
mode
---
•
•
•
711.00
Error history former 10: Error code
Reading only
2
255
1
---
mode
---
711.01
Error history former 10: Start-up meter reading
Reading only
0
999999
1
---
mode
---
711.02
Error history former 10: MMI phase
Reading only
---
---
---
---
mode
---
711.03
Error history former 10: Power value
Reading only
0%
100%
1
---
mode
---
900
Process data
920
Current PWM signal fan
Reading only
0%
100%
1%
---
mode
---
936
Normalized speed
Reading only
0%
100%
0.01%
---
mode
---
951
Mains voltage
Reading only
0 V
LME 71.000
A1: 175 V
LME 71.000
A2: 350 V
1 V
---
mode
---
954
Flame intensity
Reading only
0%
100%
1%
---
mode
---
Parameter
Modification
Value range
Resolution
Factory Set-
ting
Password
reading
level to
level
Password
writing level
to level
No.
Description
Min.
Max.
Summary of Contents for RX 150 S/PV
Page 2: ...Translation of the original instructions...
Page 48: ...20151674 46 GB Appendix Electrical panel layout 0 1 0 0 1 0 RX 150 S PV...
Page 49: ...47 20151674 GB Appendix Electrical panel layout...
Page 50: ...20151674 48 GB Appendix Electrical panel layout...
Page 51: ...49 20151674 GB Appendix Electrical panel layout 0 0 0 1 1...
Page 54: ......
Page 55: ......