Start-up, calibration and operation of the burner
6.5
Manual Backup
Tab. N
6.5.1
Error during the backup procedure
Tab. O
NOTE:
During the backup, all the parameters and settings are trans-
ferred from the unit's memory to the memory of the program
module. Only in this way, in case of replacement of the con-
trol box due to a fault, by recovering the program module
from the control box to be replaced and inserting it in the
new one, is it possible to recover all the previous settings.
Press
and
together for >1 second (Esc) to start the manual backup procedure. Parameter
PrC
is
displayed.
Display:
PrC
Press
and
to display parameter
bAC
.
Display:
bAC
Run appears during the download (backup procedure) in the program sequence.
The display shows
End
and
bAC
alternately.
The display shows the end of the data exchange.
Appears on the display for 2 minutes or can be terminated by pressing
When the backup procedure is complete the display shows
OFF
.
Press
for >1 second to reset the unit.
Display:
OFF
-
+
and
> 1s
-
+
-
+
or
-
+
nfo
1...3 s
Alternatively
/reset
nfo
> 1s
nfo
WARNING
A backup must be performed if parameters are
changed! If the backup is not performed, the safe-
ty functions and the set settings could be compro-
mised (P0, P1 and P2 values)!
The display shows
bAC
and
Er3
alternately.
For the meaning of the possible cause, see chapter List of error codes with operation via internal LED.
Alternatively
Summary of Contents for RX 150 S/PV
Page 2: ...Translation of the original instructions...
Page 48: ...20151674 46 GB Appendix Electrical panel layout 0 1 0 0 1 0 RX 150 S PV...
Page 49: ...47 20151674 GB Appendix Electrical panel layout...
Page 50: ...20151674 48 GB Appendix Electrical panel layout...
Page 51: ...49 20151674 GB Appendix Electrical panel layout 0 0 0 1 1...
Page 54: ......
Page 55: ......