20151674
34
GB
Maintenance
7.4
Recommended preventive maintenance programme
The use and maintenance instructions are meant for general ap-
plications. For specific use and maintenance instructions, contact
the manufacturer of the control box.
Checking components, monitor and indicators
DAILY
Checking adjustments of instruments and control boxes
DAILY
Checking burner flame
DAILY
Checking ignition device
WEEKLY
Checking flame signal strength
WEEKLY
Checking flame fault control system
WEEKLY
Checking firing rate command
WEEKLY
Visual and acoustic control of the pilot and fuel valves
WEEKLY
Checking fuel, venting, flue or inlet gates
MONTHLY
Test for low updraught, fan air pressure and damper position lockout
MONTHLY
Check low flame start lockout
MONTHLY
High and low gas pressure lockout test
MONTHLY
Recalibration of all the adjustment components
SIX-MONTHLY
Check of system components for detecting flame fault
SIX-MONTHLY
Check of firing rate command
SIX-MONTHLY
Check of piping and cabling of all the lockouts and shut-off valves
SIX-MONTHLY
Inspection of burner components
SIX-MONTHLY
Flame fault detection system, test for hot refractory content
YEARLY
Replacing flame rod according to the manufacturer's instruction
YEARLY
Carrying out a combustion test
YEARLY
Check of coils and diaphragms; testing other operating parts of the control valves and safety shut-off valves
YEARLY
test of the interlocking switch of the fuel valve according to the manufacturer's instructions
YEARLY
Tests for leaks on pilot valves and gas valves
YEARLY
Testing air discharge switch according to the manufacturer's instructions
YEARLY
Testing low flame starting lockout according to the manufacturer's instructions
YEARLY
For gas burners, check the sediment well and the gas filters
AS REQUIRED
Flame fault detection system, test for hot refractory content
AS REQUIRED
Tab. V
Test/Inspection
Frequency
Summary of Contents for RX 150 S/PV
Page 2: ...Translation of the original instructions...
Page 48: ...20151674 46 GB Appendix Electrical panel layout 0 1 0 0 1 0 RX 150 S PV...
Page 49: ...47 20151674 GB Appendix Electrical panel layout...
Page 50: ...20151674 48 GB Appendix Electrical panel layout...
Page 51: ...49 20151674 GB Appendix Electrical panel layout 0 0 0 1 1...
Page 54: ......
Page 55: ......