List of parameters PME71.901...)
The following pages have the Menus and the list of parameters
for setting up the LCD AZL 2 ... Display for the LME 71 ... control
box with PME 71.901 ...
The values shown in the "Factory setting" column in the table be-
low, are indicative (Control box not programmed).
A
List of parameters PME71.901...)
WARNING
To display/change the parameters it is neces-
sary to use the AZL 21 ... display kit (page 44)
accessing with the password.
Parameter
Modification
Value range
Resolution
Factory Set-
ting
Password
reading
level to
level
Password
writing level
to level
No.
Description
Min.
Max.
000
Internal parameter
41
Password for heating engineering (4 characters) Modification
xxxx
xxxx
---
---
---
OEM
42
Password OEM (5 characters)
Modification
xxxxx
xxxxx
---
---
---
OEM
60
Backup/restore
Modification
Restore
Backup
---
---
---
SO
100
General notes
102
Identification date
Reading only
---
---
---
---
mode
---
103
Identification number
Reading only
0
9999
1
0
mode
---
113
Burner identification
Modification
x
xxxxxxxx
1
burnErId
mode
SO
123
Step control min output.
Modification
1%
10%
0.1
2
SO
SO
140
Displaying the unit operation mode and display-
ing AZL2...
1 = standard (program phase)
2 = flame 1 (QRA.../ION)
3 = flame 2 (QRB.../QRC...) ® not used
4 = output active (output value)
Modification
1
4
1
4
SO
SO
164
Number of resettable start-ups
Resettable
0
999999
1
0
mode
mode
166
Total number of start-ups
Reading only
0
999999
1
0
mode
---
170.00
Switching cycles relay contact K12
Reading only
0
999999
1
0
mode
---
170.01
Switching cycles relay contact K11
Reading only
0
999999
1
0
mode
---
170.02
Switching cycles relay contact K2
Reading only
0
999999
1
0
mode
---
170.03
Switching cycles relay contact K1
Reading only
0
999999
1
0
mode
---
171
Max. relay commutation cycles
Reading only
0
999999
1
0
mode
---
200
Burner Control
224
Air pressure switch special time
Modification
0s
13.818 s
0.294 s
13.818 s
SO
OEM
225
Pre-purging time - 2.1 seconds
Modification
0s
1237 s
4.851 s
29.106 s
SO
OEM
226
Spark pre-ignition time
Modification
1.029 s
37.485 s
0.147 s
6.174 s
SO
OEM
230
Interval: End of the safety time - resetting of the
load regulator
Modification
3.234 s
74.97 s
0.294 s
9.408 s
SO
OEM
234
Post-purging time
Modification
0s
1237 s
4.851 s
19.404 s
SO
OEM
235
Air pressure switch input
0 = inactive
1 = active
Modification
0
1
1
0
SO
OEM
240.00
Repetitions meter
Limit value of flame loss during operation
Modification
0
2
1
0
SO
OEM
240.01
Repetitions meter
Limit value of No flame at the end of the safety
time
Modification
0
1
1
1
SO
OEM
241.00
Valves Seal Control
0 = OFF
1 = ON
Modification
0
1
1
1
SO
OEM
241.01
Valves Seal Control
0 = during pre-purging
1 = during post-purging
Modification
0
1
1
1
SO
OEM
241.02
Valves Seal Control
0 = according to P241.01
1 = during pre-purging and post-purging
Modification
0
1
1
0
SO
OEM
242
Evacuation of valve seal control test area
Modification
0s
2.648 s
0.147 s
2.648 s
SO
OEM
243
Atmospheric pressure valve seal control time
test
Modification
1.029 s
37.485 s
0.147 s
10.290 s
SO
OEM
244
Filling the valve seal control test area
Modification
0s
2.648 s
0.147 s
2.648 s
SO
OEM
245
Gas pressure valve seal control time test
Modification
1.029 s
37.485 s
0.147 s
10.290 s
SO
OEM
Summary of Contents for RX 150 S/PV
Page 2: ...Translation of the original instructions...