Faults - Probable causes - Solutions
Symbol
(1)
Problem
Possible cause
Recommended remedy
The burner does not start
No electrical power supply
Close all switches and check connections
A limit or safety thermostat/pressure switch
open
Adjust or replace
Control box lockout
Release the control box
Control box fuse interrupted
Replace it
(2)
Incorrect electrical wiring
Check
Defective control box
Replace
No gas supply
Open the manual valves between contac-
tor and train
Mains gas pressure insufficient
Contact your GAS COMPANY
Minimum gas pressure switch fails to close
Adjust or replace
Air pressure switch in operating position
Adjust or replace
The servomotor contact does not intervene
(closure cam 0°)
Adjust the closure cam 0°
or replace the servomotor
The burner does not
switch on, and the lock-
out appears
Flame simulation
Replace the control box
Faulty motor remote control switch
Replace
Defective electrical motor
Replace
Motor lockout
Release the thermal relay
The burner starts up but
stops at the damper
maximum opening
Do not intervene the servomotor contact
(maximum cam opening)
Cam adjustment (maximum opening)
or replace the servomotor
The burner switches on,
but then stops in lockout
Air pressure switch does not switch owing to lack of air pressure.
Air pressure switch incorrectly adjusted.
Adjust or replace
Pressure switch pressure test point pipe
blocked
Clean
Poorly adjusted head
Adjust
Dirty fan
Clean
High depression in the furnace
Contact our Technical Department
The burner turns on and
then remains in lockout
mode
Failure to the flame detection circuit
Replace the control box
The burner remains in
the pre-purge phase.
Do not intervene the servomotor contact (cam
minimum)
Cam adjustment (minimum)
or replace the servomotor
Once the pre-purging
and the safety time has
elapsed the burner goes
into lockout without the
flame appearing
Gas pressure too low
Increase pressure at governor
Ignition electrode incorrectly adjusted
Adjust it
Electrode grounded due to broken insulation
Replace
Faulty or grounded high voltage cable
Replace
High voltage cable deformed by high tempera-
ture
Replace and protect
Faulty ignition transformer
Replace
Incorrect valve or ignition transformer connec-
tions
Redo them
Defective control box
Replace
A closed valve upline the gas train
Open
The VP1 or VP2 solenoid does not open
Replace the coil or the rectfier panel
The VP1 solenoid let too little gas through
Increase
Air in pipework
Bleed air
Lockout with flame
appearing
The VS or VR solenoids let too little gas through Increase
Dirty flame sensor
Check, replace flame sensor
Faulty connection
Check, replace flame sensor
Insufficient detection current
(min.70 µA)
Measure current, replace the flame sensor
Flame sensor exhausted, faulty
Replace
Maximum gas pressure switch intervention
Adjust or replace
Defective control box
Replace