20061862
14
GB
Technical description of the burner
4.13 Servomotor (SQM10.1....)
Warnings
➤
All interventions (assembly and installation operations,
assistance, etc.) must be carried out by qualified personnel.
➤
Before modifying the wiring in the connection area of the
servomotor, fully disconnect the burner control device from
the power supply (omnipolar separation).
➤
To avoid the risk of electrocution, protect the connection ter-
minals in a suitable manner and correctly fix the cover.
➤
Check the wiring is in order.
➤
Falls and collisions can negatively affect the safety func-
tions. In this case, the servomotor must not be operated,
even if it displays no evident damage.
Assembly notes
•
Check the relevant national safety standards are respected.
•
During the assembly of the servomotor and the connection of
the damper, the gears can be disengaged by means of a le-
ver, allowing the drive shaft to be easily adjusted in both ro-
tation directions.
Technical data
Tab. H
WARNING
To avoid accidents, material or environmental
damage, observe the following instructions!
Avoid opening, modifying or forcing the actua-
tors.
Operating voltage
AC 220...240V, 50 Hz –15 % / +10 %
AC 220 V, 60 Hz –15 % / +10 %
Auxiliary and limit switch-
es switching capacity
10 (3) A, AC 24...250 V
Angular positioning
up to 160 ° (base scale)
Assembly position
optional
Protection level
IP 54, DIN 40050
Safety class
GB
Weight
approx. 1.7 kg
Actuator motor
synchronous motor
Power absorption
9 VA
Environmental conditions:
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
DIN EN 60 721-3-1
Class 1K3
Class 1M2
-20...+70°C
< 95% RH
Fig. 7
S8413
Summary of Contents for RS 1000/M C01
Page 2: ...Translation of the original instructions...
Page 51: ......